L8-06 Input Phase Loss Detection Level
Setting Range:
0.0 to 25.0% of Drives O V Trip point
Factory Default: kVA Dependent
The iQpump drive checks for a lost input phase by monitoring the DC Bus voltage ripple. After an initial delay of approximately 12
seconds, the iQpump drive will sample the DC BUS voltage every 1.28 seconds to determine the minimum and maximum voltage
readings. The difference between the minimum and maximum voltage is averaged over ten consecutive scans. If this “averaged” value is
greater than the trip level as determined by L8-06 (L8-06 x 400 for 200 volt class Drives; L8-06 x 800 for 400 volt class Drives) the
iQpump drive shuts down and displays “PF,” an input phase loss fault.
Figure 1.93
Figure 98 Input Phase Loss Detection Diagram
■
L8-07 Output Phase Loss Protection
<0033>
The output phase loss detection circuit monitors the DCCT and activates when one or more of the output phases are lost. The detection
circuit calculates the RMS current value (I
RMS
) for each of the phases and compares it with an internal output detection level. If I
RMS
decreases to or below the detection level for 10 seconds, an output phase loss (LF) fault occurs and the motor coasts to a stop
■
L8-09 Output Ground Fault Detection Selection
The iQpump drive has a ground fault detection circuit that activates when the current to ground exceeds 50% of the Drive’s rated output
current. The current to ground is determined by comparing the measured current on each of the output phases. If the current to ground is
determined to be above 50% of the Drive’s rated output current the digital operator will display a GF and the iQpump drive will coast to
stop.
■
L8-10 Heatsink Cooling Fan Operation Selection
Refer to L8-11 description.
Setting
Description
0
Disabled
1
Enabled (
factory default
)
Setting
Description
0
Disabled
1
Enabled
(factory default
)
Setting
Description
0
Fan On-Run Mode (
factory default
)
1
Fan Always On
t
L8-06
Phase Loss
Fault Signal
DC Bus
Voltage
10 seconds
Fault Contact
t
Closed
Open
Input Phase Loss
Time
Содержание iQpump Series
Страница 1: ...iQpump Drive Programming Manual Document Number TM iQp 02...
Страница 204: ...204 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 208: ...208 YASKAWA TM iQp 02 iQpump Drive Programming Manual THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 209: ...YASKAWA TM iQp 02 iQpump Drive Programming Manual 209 THIS PAGE INTENTIONALLY LEFT BLANK...