200
HB700 | CPU | PMC921xEx | en | 24-04
Web-based management - WBM
iC9200 Series
Security > User Authentication
Enable or disable Syslog
configuration
3.
Specify the following parameters at Filter Options:
■
Facilities
–
Here you specify the system type of the log data.
■
Severity Level
–
Determine here the severity level from which the log data is sent to the
Syslog server.
Level 1: >= Internal (debug): All messages are sent.
Level 2: >= Information (info): Messages >= level 2 are sent.
Level 3: >= Warning (warning): Messages >= level 3 are sent.
Level 4: >= Error (err): Messages >= level 4 are sent.
Level 5: >= Critical Error (crit): Messages >= level 5 are sent.
Level 6: >= Fatal Error (alert): Messages >= level 6 are sent.
Level 7: Emergency (emerg) Only emergency messages are sent.
4.
Click at [OK].
🡆
The dialog is closed and the Syslog server is listed in the table.
You can remove entries with and edit them with .
Syslog Configuration
Security
Security
Certificate Authentication
Firewall
SD Card
Syslog Configuration
User Authentication
Information
Diagnostics
Configuration
Administration
iC92...
PMC92...
1.
By selecting or deselecting the control field of
‘Syslog Server Destination Activation’
at
‘Syslog Configuration’
you can enable respectively disable the Syslog server
targets specified in the table.
2.
Click on [Apply].
🡆
The settings are accepted.
6.5.5
User Authentication
■
At
‘User Authentication’
you can enable or disable user authentication.
■
If user authentication is enabled, you have access to definable components of the
CPU and functions in iCube Engineer exclusively by specifying user name and pass-
word.
■
If user authentication is disabled, access takes place without a user query. The areas
for the administrator remain password-protected.
−
By default user authentication is enabled. On delivery, the "Admin"
user is already created with administrator rights.
−
Please note that by disabling the user authentication you endanger
the security of your system against unauthorized access!
−
Use the administrator password printed on the CPU only for the initial
login to the WBM.
−
After you have successfully logged in, you should change the admin-
istrator password for security reasons.
Содержание iC9200 Series
Страница 211: ...7 Appendix...
Страница 212: ......
Страница 214: ...214 HB700 CPU PMC921xEx en 24 04 Checklists Deployment CPU iC921xM FSoE iC9200 Series...