3.5 SERVOPACK Installation
3.5.1 Installation Precautions
3-8
3.5
SERVOPACK Installation
3.5.1
Installation Precautions
Environmental Conditions
Refer to the following section for the installation conditions.
Surrounding Air Temperature
Design the size of the control panel, the SERVOPACK installation, and the cooling method so
that the temperature surrounding the SERVOPACK does not exceed 40
°
C.
Installation Near Sources of Heat
Implement measures to prevent temperature increases caused by radiant or convection heat
from heat sources so that the temperature around the SERVOPACK meets the environmental
conditions.
Installation Near Sources of Vibration
Install a vibration absorber on the installation surface of the SERVOPACK so that the SERVO-
PACK will not be subjected to vibration.
Other Conditions
Do not install the SERVOPACK in a location subject to high temperatures, high humidity, water
drops, cutting oil, excessive dust, excessive dirt, excessive iron powder, corrosive gasses, or
radioactivity.
Installing One SERVOPACK
Observe the following mounting conditions to ensure the necessary space to cool the SERVO-
PACK.
Studs
Device mounting surface
15 mm min.
10 mm min.
10 mm min.
SERVOPACK
20 mm min.