User Parameter Tables
5-
35
E1-04
Maximum
Output
Frequency
These parameters are only applicable
when V/f Pattern Selection is set to
Custom (E1-03 = F or FF). To set V/f
characteristics in a straight line, set
the same values for E1-07 and E1-09.
In this case, the setting for E1-08 will
be disregarded. Be sure that the four
frequencies are set in the following
manner or else an OPE10 fault will
occur:
E1-04 (FMAX)
E1-11
E1-06 (FA)
> E1-07 (FB)
E1-09 (FMIN)
Note: Setting parameter E1-01 to
zero is also acceptable
40.0
to
400.0
*5
60.0Hz
*2
No
Q
Q
Q
Q
Q
303H
Max
Frequency
E1-05
Maximum
Output
Voltage
0.0
to
255.0
(240V)
0.0
to
510.0
(480V)
230.0V
or
460.0V
No
Q
Q
Q
Q
Q
304H
Max
Voltage
E1-06
Base
Frequency
0.0
to
400.0
*5
60.0Hz
*2
No
Q
Q
Q
Q
Q
305H
Base
Frequency
E1-07
Mid.
Output
Frequency A
0.0
to
400.0
3.0Hz
*2
No
A
A
A
No
No
306H
Mid
Frequency
A
E1-08
Mid.
Output
Voltage A
0.0
to
255.0
(240V)
0.0
to
510.0
(480V)
12.6
Vac
or
25.3
Vac
*2
No
A
A
A
No
No
307H
Mid
Voltage A
E1-09
Minimum
Output
Frequency
0.0
to
400.0
*5
0.5Hz
*2
No
Q
Q
Q
A
Q
308H
Min
Frequency
E1-10
Minimum
Output
Voltage
0.0
to
255.0
(240V)
0.0
to
510.0
(480V)
2.3 Vac
or
4.6 Vac
*2
No
A
A
A
No
No
309H
Min
Voltage
E1-11
Mid.
Output
Frequency B
Set only when the V/F pattern is
finely adjusted in the constant
power (HP) area above base speed.
Adjustment is not normally
required.
0.0
to
400.0
*5
0.0Hz
*3
No
A
A
A
A
A
30AH
Mid
Frequency
B
E1-12
Mid.
Output
Voltage B
0.0
to
255.0
(240V)
0.0
to
510.0
(480V)
0.0
Vac
*3
No
A
A
A
A
A
30BH
Mid
Voltage B
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
Output voltage (V)
Frequency (Hz)