User Parameter Tables
5-
41
Option Parameters: F
The following settings are made with the option parameters (F parameters): Settings for Option Cards.
PG Option Setup: F1
User parameters for the PG Speed Control Card are shown in the following table.
Parameter
Number
Name
Description
Setting
Range
Factory
Setting
Change
during
Operation
Control Methods
MODBUS
Register
Display
V/f
V/f
with
PG
Open
Loop
Vector
1
Flux
Vector
Open
Loop
Vector
2
F1-01
PG Parameter Sets the number of pulses per
revolution (PPM) of the
encoder (pulse generator).
0
to
60000
1024
No
No
Q
No
Q
No
380H
PG Pulses/
Rev
F1-02
Operation
Selection at
PG Open
Circuit
(PGO)
Sets stopping method when a
PG open circuit fault (PGO)
occurs. See parameter F1-14.
0: Ramp to stop - Decelerate
to stop using the active
deceleration time.
1: Coast to stop
2: Fast - Stop - Decelerate to
stop using the deceleration
time in C1-09.
3: Alarm Only - Drive
continues operation.
0 to 3
1
No
No
A
No
A
No
381H
PG Fdbk
Loss Sel
F1-03
Operation
Selection at
Overspeed
(OS)
Sets the stopping method
when an overspeed (OS)
fault occurs. See F1-08 and
F1-09.
0: Ramp to stop - Decelerate
to stop using the active
deceleration time.
1: Coast to stop
2: Fast - Stop - Decelerate to
stop using the deceleration
time in C1-09.
3: Alarm Only - Drive
continues operation.
0 to 3
1
No
No
A
No
A
A
382H
PG
Overspeed
Sel
F1-04
Operation
Selection at
Deviation
Sets the stopping method
when a speed deviation
(DEV) fault occurs.
See F1-10 and F1-11.
0: Ramp to stop - Decelerate
to stop using the active
deceleration time.
1: Coast to stop
2: Fast - Stop - Decelerate to
stop using the deceleration
time in C1-09.
3: Alarm Only - Drive
continues operation.
0 to 3
3
No
No
A
No
A
A
383H
PG
Deviation Sel
Содержание CIMR-G7U