2
-12
4/0
100
M10
100 - 10
M12
100 - 12
M16
100 - 16
250 / 300MCM
125 / 150
M10
150 - 10
M12
150 - 12
M16
150 - 16
400MCM
200
M12
200 - 12
650MCM
325
M12 x 2
325 - 12
M16
325 - 16
*
Wire sizes are based on 75 degrees Celsius copper wire.
** Equivalent connector can be used.
IMPORTANT
Determine the wire size for the main circuit so that line voltage drop is within 2% of the rated voltage. Line
voltage drop is calculated as follows:
Line voltage drop (V) =
x wire resistance (W/km) x wire length (m) x current (A) x 10
-3
Wire Size *
Terminal Screw
Ring Tongue (R-Type) Closed-Loop Connectors (Lugs)
JST Corporation Part Numbers **
3