Test Run Procedure
Test run the MxC as shown in the flowchart below:
Fig 4.1 Test Run Flowchart
START
Installation
Wiring
Turn on power.
Confirm status.
Basic settings
(Quick Programming Mode)
Select operating
method.
Settings according
to control method
Application settings
(Advanced Programming Mode)
No-load operation
Loaded operation
Optimum adjustments and
Parameter settings
Check/save parameters.
END
YES
V/f
(A1-02 = 0)
Vector (A1-02 = 2 or 3) *2
Set E1-03.
V/f default: 200 V/60 Hz(400 V/60 Hz)
YES
NO
V/f Control?
Motor cable over
50 m or heavy load possibly
causing motor to stall or
overload?
Stationary Auto-Tuning for
line-to-line resistance only
Rotational Auto-Tuning *3
*1
*1 If the motor cable changes to 50 m or longer for the actual
installation, perform stationary Auto-Tuning for the line-to-line
resistance only on-site.
*2 The default control method is Open Loop Vector Control
(A1-02 = 2).
*3 If the maximum output frequency is different from the base
frequency, set the Maximum Output Frequency (E1-04) to the
value of the base frequency after Auto-Tuning.