7
-8
EF10
Ext Fault
S10
External Fault (Input Terminal S10)
An “external fault” was input from a
multi-function input terminal.
• Reset external fault inputs to the
multi-function inputs.
• Remove the cause of the exter-
nal fault.
EF11
Ext Fault
S11
External Fault (Input Terminal S11)
EF12
Ext Fault
S12
External Fault (Input Terminal S12)
SVE
Zero Servo
Fault
Zero-servo Fault
The rotation position moved during
zero-servo operation.
The torque limit is too small.
Increase the limit.
The load torque is too large.
Reduce the load torque.
-
Check for signal noise.
OPR
Oper Dis-
connect
Digital Operator Connection Fault
The connection to the digital operator
was broken during run for a Run Com-
mand from the digital operator.
-
Check the connection to the digi-
tal operator.
CE
Memobus
Com Err
MEMOBUS Communications Error
A normal reception was not possible
for 2 s or longer after control data was
received once.
-
Check the communications
devices and communications sig-
nals.
BUS
Option
Com Err
Option Communications Error
A communications error was detected
during a Run Command or while set-
ting a frequency reference from a
Communications Option Card.
-
Check the communications
devices and communications sig-
nals.
CPF00
CPF
Digital Operator Communications
Error 1
Communications with the digital oper-
ator were not established within 5 sec-
onds after the power was turned on.
The digital operator's connector isn't
connected properly.
Disconnect the digital operator
and then connect it again.
The MxC's control circuits are faulty.
Replace the MxC.
CPU External RAM Fault
-
Try turning the power supply off
and on again.
The control circuits were destroyed.
Replace the MxC.
CPF01
CPF01
Digital Operator Communications
Error 2
After communications were estab-
lished, there was a communications
error with the digital operator for more
than 2 seconds.
The digital operator isn't connected
properly.
Disconnect the digital operator
and then connect it again.
The MxC's control circuits are faulty.
Replace the MxC.
CPF03
EEPROM
Error
EEPROM Error
-
Try turning the power supply off
and on again.
The control circuit is damaged.
Replace the MxC.
CPF04
Internal
A/D Err
CPU Internal A/D Converter Error
-
Try turning the power supply off
and on again.
The control circuit is damaged.
Replace the MxC.
CPF05
External
A/D Err
CPU External A/D Converter Error
-
Try turning the power supply off
and on again.
The control circuit is damaged.
Replace the MxC.
Table 7.1 Fault Displays and Processing (Continued)
Display
Meaning
Probable Causes
Corrective Actions