Individual Functions
This section explains the individual functions used in special applications.
Using MEMOBUS Communications
The serial communications with MEMOCON-series Programmable Controllers (PLCs) or similar devices can
be performed using the MEMOBUS protocol.
MEMOBUS Communications Configuration
MEMOBUS communications are configured using 1 master (PLC) and a maximum of 31 slaves. Serial com-
munications between master and slave are normally started by the master, and the slave responds.
The master performs signal communications with one slave at a time. Consequently, be sure to set the address
of each slave beforehand, so the master can perform signal communications using that address. Slaves Receiv-
ing Commands from the master perform the specified function, and send a response to the master.
Fig 6.57 Example of Connections between PLC and MxC
Communications Specifications
The MEMOBUS communications specifications are shown in the following table.
Item
Specifications
Interface
RS-422, RS-485
Communications Cycle
Asynchronous (Start-stop synchronization)
Communications Parameters
Baud rate
Select from 1200, 2400, 4800, 9600, and 19200 bps.
Data length
8 bits fixed
Parity
Select from even, odd, or none.
Stop bits
1 bit fixed
Communications Protocol
MEMOBUS (RTU Mode only)
Number of Connectable Units
31 units max (when using RS-485)
MxC
MxC
MxC
MEMOCON-series PLC
RS-485 connections
example