TROUBLESHOOTING
YDG Operation Manual
63
34127
Generator
No electricity generated
Main switch is off
Turn main switch on
Equipment incorrectly connected
to generator
Connect the equipment correctly
–
Defective AVR
See authorized YANMAR
industrial engine dealer or
distributor
–
Winding short circulated or loose
connections
–
Electrical load too high
Reduce electrical load
–
Loss of residual magnetism
See authorized YANMAR
industrial engine dealer or
distributor
–
Engine speed too low
–
Defective rotor diode
See authorized YANMAR
industrial engine dealer or
distributor
Defective stator
–
Defective rotor
–
Engine not running properly
–
Lack of no-load voltage
Demagnetized machine
See authorized YANMAR
industrial engine dealer or
distributor
–
AVR fuse interrupted
–
Faulty AVR
–
Winding failure
–
Insulation failure
–
Wrong or incorrectly carried out
connections
–
Too low or too high no-load
voltage
Faulty AVR
–
Winding failure
–
Faulty slip-ring
–
Too low load voltage
Faulty AVR
See authorized YANMAR
industrial engine dealer or
distributor
–
Possible overload
Check load current value
–
Too high load voltage
Faulty AVR
See authorized YANMAR
industrial engine dealer or
distributor
–
Unstable voltage
Faulty AVR
See authorized YANMAR
industrial engine dealer or
distributor
–
Protections activated
Turn off and restart the
equipment
–
Overheating
Possible overload
Check load current value
–
Alternator inlet or outlet openings
are clogged
See authorized YANMAR
industrial engine dealer or
distributor
–
Noisy alternator
Bearing broken
See authorized YANMAR
industrial engine dealer or
distributor
–
Symptom
Probable cause
Action
Refer to
Содержание YDG Series
Страница 10: ...INTRODUCTION viii YDG Operation Manual This Page Intentionally Left Blank ...
Страница 14: ...TABLE OF CONTENTS xii YDG Operation Manual This Page Intentionally Left Blank ...
Страница 36: ...PRODUCT OVERVIEW 22 YDG Operation Manual This Page Intentionally Left Blank ...
Страница 56: ...GENERATOR OPERATION 42 YDG Operation Manual This Page Intentionally Left Blank ...
Страница 82: ...TROUBLESHOOTING 68 YDG Operation Manual This Page Intentionally Left Blank ...
Страница 92: ...YIYDG EN0000 2021 10 YANMAR ITALY S p A http www yanmaritaly it ...