G.F.C.I. Receptacle Test
1. Start the engine.
2. Turn the AC switch (N.F.B.) to “I” (ON).
3. Press the test button, then check the position of
the reset button.
1
Reset button
2
Test button
G.F.C.I. reset
button position
after test
G.F.C.I. receptacle
operation
3
Pop out
Correct
4
Stay in
Incorrect
4. If G.F.C.I. operation is correct, push in the reset
button.
If the G.F.C.I. operates incorrectly, consult a
Yamaha dealer.
WARNING
Do not operate the generator with a faulty G.F.C.I.
circuit. Electric shock could occur. Have the gener-
ator repaired by a qualified mechanic.