Frequency-controlled hoist motors 4HS.-MF 100 Hz
100 Hz
Hoist motor
*2
Power
Duration factor
Nominal current
Main fuse CC / J
*1
380…415
V
500…525
V
-
380…415
V
500…525
V
-
[HP]
CDF [%]
I
N
[A]
[A]
4HS3
3.9
80
8.3
6.6
-
15
10
-
4.8
70
9.3
7.4
-
6
60
10.7
8.6
-
4HS5
8
80
15.5
12.4
-
25
15
-
10.1
70
18.0
14.4
-
12.1
60
21.0
16.8
-
4HS7
16.1
80
24.0
19.2
-
50
25
-
20.1
70
28.0
22.4
-
24.1
60
34.0
27.2
-
4HS8
24.1
70
34.0
27.2
-
50
30
-
30.8
60
42.0
33.6
-
4HSA
37.5
70
57.0
45.6
-
80
50
-
46.9
60
64.0
51.2
-
Tab. 48
11.2.8
Frequency-controlled hoist motors 4HS.-MF 120 Hz
120 Hz
Hoist motor
*2
Power
Duration factor
Nominal current
Main fuse CC / J
*1
440…480
V
575…600
V
440…480
V
575…600
V
[HP]
CDF [%]
I
N
[A]
[A]
4HS3
4.7
80
8.1
6.5
15
10
5.8
70
9.3
7.4
7.2
60
10.8
8.6
4HS5
9.7
70
17.0
13.6
25
15
12.1
60
19.0
15.2
14.8
60
22.0
17.6
4HS7
18.8
80
23.0
18.4
50
25
24.1
70
26.0
20.8
28.2
60
36.0
28.8
4HS8
28.2
70
36.0
28.8
50
30
36.2
60
44.0
35.2
4HSA
45.6
70
56.0
44.8
80
50
56.3
60
65.0
52.0
Tab. 49
*1 Protection not 100 % with CC / J, we recommend additional semiconductor fuses.
*2 The motors are designed for rated voltage ranges. In accordance with EN 60034 a voltage tolerance of
±5 % and a frequency tolerance of ±2 % apply on top of the rated voltage ranges. If these are fully utilized,
the permissible limit temperature of the temperature class may be exceeded by 10 K. The maximum current
occurring in the rated voltage range is given.