35
Dissolved Oxygen Transmitter
GB Oxix Manual 1209
FW: 841013-009, 846001-002, 841513-009
Wiring Schematic #2
for "Oxix
®
with Blind Lid and a Magflux
®
with Blind Lid connected to a com-
mon wall mounted Display Unit" on the opposite page (page
34
).
Oxix
®
with Blind Lid
2-wire, shielded twisted cable
1. Connect lead "1" to slot "Display A"
2. Connect lead "2" to slot "Display B"
3. Connect the twisted shield to slot
"Display -"
Magflux
®
with Blind Lid
2-wire, shielded twisted cable
1. Connect lead "1" to slot "Display A"
2. Connect lead "2" to slot "Display B"
3. Connect the twisted shield to slot
"Display -".
4-wire, shielded twisted cable
1. Connect lead "1" to slot "D"
2. Connect lead "2" to slot "Display A"
3. Connect lead "3" to slot "Display B"
4. Connect the twisted shield to slot
"Display -".
Wall Mounted Display Unit
4-wire, shielded twisted cable
1. Connect lead "1" to slot "D"
2. Connect lead "2" to slot "Display A"
3. Connect lead "3" to slot "Display B"
4. Connect the twisted shield to slot
"Display -".
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
A
B
207920
1 2 3 4 5 6 7 8 9
1 2 3 4 5 6 7 8 9
Mains
supply
-mA-
-D02-
-D01-
-DI-
-Display-
+
+
A
B
C2 N02
C NO
N01
PE
N
L
-
-
C1
Line
2 wire
shielded cable.
4 wire
shielded cable.
displa
y unit
displa
y unit
Display unit
Converter #4
Converter #1
Max. four MJK converters with Modbus
can be connected to one display unit:
521274
2,5
Main supply
Supply
Fuse
10-30
V DC
1 A
T
24
V A
C
500 mA
T
115
V A
C
125 mA
T
230
V A
C
63 mA
T
Sensor supply
Fuse 200 mA T
+DC
GND A
B
Red
Black
White
Gr
een
Shield
521275
www.mjk.com
DK: +45 45 56 06 56
NO: +47 69 20 60 70
SE: +46 53 31 77 50
NL: +31 251 672171
USA: +1 847 482 8655
AUS: +61 3 9758 8533
1 2 Shield
4 and
shield
1 2 Shield
1 2 3
1 2 3