Pa-
ram-
eter
Description
Range
Unit of
meas-
urement
Default
0=no action
1=invert the di-
rection of rota-
tion
WARNING:
If the parameter
EL
=0 and
MP
=0, the
pump is not protected against dry run-
ning. The warranty does not cover dam-
age to the electric pump caused by in-
correct configuration.
• For motor cables longer than 30 m, it may be
necessary to increase motor current by 10%.
Check this in relation to the type of installation
and cable.
• Example: In=5A, set the parameter at 5.5A.
Table 18: Models MMA and MTA
Param-
eter
Description
Range Unit of
meas-
ure-
ment
Default
LAN-
GUAGE
Language se-
lection
ITAL-
IAN
ENG-
LISH
GER-
MAN
FRENC
H
SPAN-
ISH
DUTCH
POR-
TU-
GUESE
POL-
ISH
TURK-
ISH
GREEK
-
ITAL-
IAN
NOM.C
URR
Set the cur-
rent rating
value of the
pump motor
on the data
plate.
0.1 to
6.0
(MMA0
6)
0.1 to
12.0
(MMA1
2)
0.1 to
6.0
(MTW0
6)
0.1 to
10.0
(MTW1
0)
Ampere Imax
Param-
eter
Description
Range Unit of
meas-
ure-
ment
Default
ROTA-
TION
For three-
phase motors,
invert the di-
rection of ro-
tation.
0=no action
1=invert the
direction of
rotation
0 / 1
-
0
MIN.FR
EQ
Minimum
start-up and
stop frequen-
cy of the mo-
tor. Frequen-
cy at which
the converter
begins to run
(upon start-up
and shut-
down) without
using the
ramps.
15 to
48,
three-
phase
motor
30 to
48, sin-
gle-
phase
motor
Hz
30
EXT.LO
W WA-
TER
Enable the
digital input
and connect
the level sen-
sor to ensure
that the pump
stops when
there is no
water. See
(refer to figure
5.7). Alarm
A1
if parame-
ter
EXT.LOW
WATER
=YES
and the elec-
trical contact
is open.
NO:
Disa-
bled, no
control
YES:
Ena-
bled
-
NO
SET
PRESS
Set the re-
quired pres-
sure value of
the system
(set point)
0.0 to
10
0.0 to
16
(in rela-
tion to
the full
scale of
the
sensor)
bar
2.5
MIN.PR
ESS
Pressure val-
ue of the sys-
tem below
which the
A4
"minimum
pressure"
alarm is trig-
gered. When
the alarm is
triggered, the
pump stops
and the ART
0.0 to
(
SET
PRESS
-0.4)
0.0 =
Disa-
bled
bar
0.0
en - Original instructions
35
Содержание Lowara ResiBoost MMW Series
Страница 224: ...9 inst e_01 SC 10 inst g_05 SC 2x 2x 2x 2x 3x 3x 2x 2x MMW MTW MMA MTA 2 1 it en fr de es pt nl pl el tr 224 ...
Страница 225: ...11 L N V U W V U L N 1 MMA 2 1x230V 3x230V MTA 2 1 L N L N INST E_MMA 02_B SC 1 2 1 2 it en fr de es pt nl pl el tr 225 ...
Страница 227: ...13 L N L N V U W V U L N 1 2 MMW 1 2 1x230V 3x230V MTW L N INST E_MMW 02_B SC 1 2 it en fr de es pt nl pl el tr 227 ...
Страница 229: ...15 4 20mA QCL5 Max Min Max Min G WH BN inst m_03 SC BP it en fr de es pt nl pl el tr 229 ...
Страница 234: ...22 INST G_11_B SC 7 6 5 4 3 2 1 13 8 11 12 2 10 11 2 14 15 it en fr de es pt nl pl el tr 234 ...
Страница 235: ...23 INST G_12_B SC 1 2 7 15 14 6 5 4 3 8 9 2 10 11 12 18 13 it en fr de es pt nl pl el tr 235 ...
Страница 236: ...24 INST G_13_B SC 2 1 13 8 11 12 2 10 11 2 14 15 16 11 17 it en fr de es pt nl pl el tr 236 ...
Страница 237: ...25 13 15 14 INST G_14_B SC 8 9 2 1 2 10 11 12 18 17 16 11 it en fr de es pt nl pl el tr 237 ...
Страница 238: ...26 INST G_06_B SC 3 9 6 2 4 1 6 QCL5 5 8 2 2 2 1 m B 10 m 3 m A 7 it en fr de es pt nl pl el tr 238 ...
Страница 240: ...28 INST G_08_B SC 3 9 6 2 4 1 6 QCL5 5 8 2 2 2 1 m B 10 m 3 m A 7 it en fr de es pt nl pl el tr 240 ...
Страница 243: ......