ART function (Automatic Reset Test)
When alarm
A4
PRESS MIN
is triggered with the
LED (8) illuminated, the converter performs automat-
ic reset tests on the electric pump.
The system does the following:
The converter enters
A4PRESS MIN
fault mode with
the LED (8) illuminated. Approximately 5 minutes af-
ter the alarm, the system attempts to start the elec-
tric pump to try to increase the pressure up to the
value set in the
MP
parameter for the models MMW
and MTW or in the
PRESS MIN
value for the models
MMA and MTA. See
. If the pressure in the system exceeds the val-
ue, the alarm disappears and the electric pump is
ready without any faults and with the LED (8) off. If
the
A4
alarm is still active with the LED (8) illuminat-
ed, the system runs the automatic reset procedure
described above once every 30 minutes over the
next 24 hours. If the
A4
alarm perseveres after
these attempts, the system remains in this disabled
condition with the LED (8) illuminated until an opera-
tor resolves the problem. During the ART attempts, it
is possible to reset the
A4
alarm as follows:
• Press (2) to enter MANUAL mode.
• Press (6) to reset the alarm and turn off the LED
(8).
• Start up the pump, press (1) and check that the
pressure reaches or exceeds the set MINIMUM
PRESSURE value. If this does not happen, stop
the pump and resolve the problem.
• Enter AUTOMATIC mode and press (2).
All the models of the converter, MMW, MTW, MMA,
and MTA, have the ART function. To disable the
ART function, it is necessary to disable the MINI-
MUM PRESSURE control (alarm A4).
AIS function (de-icing)
The AIS function is ONLY available for the MMW
and MTW models of the converter and cannot be
disabled.
The following conditions are possible:
• In AUTOMATIC mode, with the system in stand-
by, the electric pump stopped and the pressure of
the system at or above the set point pressure. If
the temperature of the power module is ≤ 10°C
(water temperature ≈1°C) the pump starts up au-
tomatically and stops when the temperature of
the module reaches ≈ 15°C.
• Electric pump already running in AUTOMATIC
mode with the pressure of the system at or
above the set point pressure. If the temperature
of the power module is ≤ 10°C (water tempera-
ture ≈ 1°C) the pump does not stop but continues
to run until the temperature of the module reach-
es ≈ 15°C.
6 Alarms
6.1 Alarms and warnings
When an alarm is triggered or the pump is locked,
the fault LED (8) is illuminated and steady and the
electric pump is at standstill.
WARNING:
In this case, the system is in AUTOMAT-
IC mode. If the converter is turned off
and on again, it runs in AUTOMATIC
mode.
The last alarm is shown on the display. It is possible
for several alarms to be triggered at the same time.
To start the pump:
1. Press (2) to enter MANUAL mode.
2. Press (5) to view the types of faults in progress,
if there is more than one.
3. Eliminate the cause of the faults.
4. Press (6) to reset the system (alarms) and the
LED (8) turns off.
5. Press (2) to set AUTOMATIC mode and the
pump starts up if the pressure of the system is
below the set point. This resets the alarms and,
if an alarm is still active, the LED (8) is illuminat-
ed and the pump is still locked. Repeat steps 1–
5.
WARNING:
• Alarm
A1
no water and
A4
minimum
pressure are not available in manual
mode and it is possible to press (1) to
run the pump.
• Alarms
A3
,
A5
,
A6
,
A7
,
A8
,
A9
are
available in MANUAL mode and
when an alarm is triggered, the LED
(8) is illuminated and the pump can-
not be started by pressing (1).
• Alarm
A2
: if the system is in manual
mode and (1) has been pressed to
run the pump, the pump stops and
the LED (8) is illuminated when the
absorbed current exceeds the set val-
ue.
6.1.1 List of alarms
N°
Text on
the dis-
play (*)
Model
Descrip-
tion
Reset
A1
WATER
LACK
MMW
MTW
MMA
MTA
No flow
of water
to the
pump.
Automat-
ic, when
the alarm
stops
Causes:
1. No flow of water on the intake side of the pump.
The pump must not run dry because this causes
severe damages.
2. For the MMW and MTW the
EL
parameter is
enabled and the digital input is open. See
3. For the MMA and MTA the
EXT.LOW WATER
parameter is enabled and the digital input is
AUTOMATIC mode: Alarm triggered and pump
locked. It is possible to run the pump in manual
mode (2) when the alarm is triggered: press (6),
make sure the LED (8) is off, and press (1). The
pump can be run and primed in this way, but it is im-
portant not to run it on dry for more than 5 seconds.
Solutions:
en - Original instructions
38
Содержание Lowara ResiBoost MMA Series
Страница 197: ...N 254 V 2 5 DC Bus N A9 T MMW MTW MMA MTA 184 V 7 7 1 MMW MTW MMA MTA A 30m EL SP el 197...
Страница 200: ...30 mA RCD B 9 9 1 LED el 200...
Страница 224: ...9 inst e_01 SC 10 inst g_05 SC 2x 2x 2x 2x 3x 3x 2x 2x MMW MTW MMA MTA 2 1 it en fr de es pt nl pl el tr 224...
Страница 225: ...11 L N V U W V U L N 1 MMA 2 1x230V 3x230V MTA 2 1 L N L N INST E_MMA 02_B SC 1 2 1 2 it en fr de es pt nl pl el tr 225...
Страница 227: ...13 L N L N V U W V U L N 1 2 MMW 1 2 1x230V 3x230V MTW L N INST E_MMW 02_B SC 1 2 it en fr de es pt nl pl el tr 227...
Страница 229: ...15 4 20mA QCL5 Max Min Max Min G WH BN inst m_03 SC BP it en fr de es pt nl pl el tr 229...
Страница 234: ...22 INST G_11_B SC 7 6 5 4 3 2 1 13 8 11 12 2 10 11 2 14 15 it en fr de es pt nl pl el tr 234...
Страница 235: ...23 INST G_12_B SC 1 2 7 15 14 6 5 4 3 8 9 2 10 11 12 18 13 it en fr de es pt nl pl el tr 235...
Страница 236: ...24 INST G_13_B SC 2 1 13 8 11 12 2 10 11 2 14 15 16 11 17 it en fr de es pt nl pl el tr 236...
Страница 237: ...25 13 15 14 INST G_14_B SC 8 9 2 1 2 10 11 12 18 17 16 11 it en fr de es pt nl pl el tr 237...
Страница 238: ...26 INST G_06_B SC 3 9 6 2 4 1 6 QCL5 5 8 2 2 2 1 m B 10 m 3 m A 7 it en fr de es pt nl pl el tr 238...
Страница 240: ...28 INST G_08_B SC 3 9 6 2 4 1 6 QCL5 5 8 2 2 2 1 m B 10 m 3 m A 7 it en fr de es pt nl pl el tr 240...
Страница 243: ......