technicians and in compliance with
the regulations in force.
• Before starting work on the unit,
make sure that the unit and the con-
trol panel are isolated from the power
supply and cannot be energized.
Grounding (earthing)
Electrical Hazard:
• Always connect the external protec-
tion conductor to ground (earth) ter-
minal before making other electrical
connections.
4.4.1 Power supply connection
WARNING:
Always turn off the power supply and
wait a minimum of 2 minutes before
making any connections.
The converter comes with a mains power cable and
a motor power cable. Some models have a power
supply cable with mains plug. See
the pump making sure that the plug and socket can
be easy to access for deactivating the con
pump system.
If the power cable of the motor needs to be re-
placed, fit a new one of a cross-section suited to the
maximum current consumption of the electric motor
and taking into account also the maximum voltage
drop (≤4%). Refer to
for the
minimum characteristics of the H07RNF cables in
relation to the model of the converter and the length
of the cable. Maximum cross-section 4mm
2
ana-
lyzed.
Install or replace the power
cables
For models MMW and
MTW, see
.
1. Unfasten the 4
screws and open the
REAR cover.
2. Insert the power ca-
bles in the relative
cable glands.
3. First connect the
ground cable to the
relative terminal and
then the other ca-
bles. It is good prac-
tice for the ground
cable to be longer
than the other ca-
4. Check that all the ca-
bles are secured,
close the REAR cov-
er and fasten the
screws.
For models MMA and
MTA, see
.
1. Unfasten the 8
screws and open the
FRONT cover mak-
ing sure not to dam-
age the connecting
cable of the display
and the connector.
2. Insert the power ca-
bles in the relative
cable glands.
, and
3. First connect the
ground cable to the
relative terminal and
then the other ca-
bles. It is good prac-
tice for the ground
cable to be longer
than the other ca-
bles.
4. Check that all the ca-
bles are secured, in-
cluding the connect-
ing cable of the dis-
play, and close the
FRONT cover and
fasten the screws.
WARNING:
• The power cable of the motor must
NEVER be laid parallel to the power
cable of the converter, see
• Models MTW and MTA: although the
converter has a single-phase power
supply, the pump motor always has a
three-phase power supply at 230 V.
The missing phases are created by
the converter. For additional informa-
4.4.2 I/O connections
For models MMW and
MTW, see
.
1. Unfasten the 6
screws and open the
FRONT cover.
2. If required, connect
the cable of the level
sensor to the digital
input to prevent dry
running of the pump.
The electrical con-
tact must be normal-
ly open when an
alarm is triggered.
Suitable cable 2 x
(0.75 to 1.5) mm
2
.
3. Insert the cable in
the cable gland in
the cover, see
.
4. Check that all the ca-
bles are secure and
close the FRONT
cover, making sure
not to crush the ca-
bles between the
cover and the con-
verter. Unfasten the
6 screws.
en - Original instructions
30
Содержание Lowara ResiBoost MMA Series
Страница 197: ...N 254 V 2 5 DC Bus N A9 T MMW MTW MMA MTA 184 V 7 7 1 MMW MTW MMA MTA A 30m EL SP el 197...
Страница 200: ...30 mA RCD B 9 9 1 LED el 200...
Страница 224: ...9 inst e_01 SC 10 inst g_05 SC 2x 2x 2x 2x 3x 3x 2x 2x MMW MTW MMA MTA 2 1 it en fr de es pt nl pl el tr 224...
Страница 225: ...11 L N V U W V U L N 1 MMA 2 1x230V 3x230V MTA 2 1 L N L N INST E_MMA 02_B SC 1 2 1 2 it en fr de es pt nl pl el tr 225...
Страница 227: ...13 L N L N V U W V U L N 1 2 MMW 1 2 1x230V 3x230V MTW L N INST E_MMW 02_B SC 1 2 it en fr de es pt nl pl el tr 227...
Страница 229: ...15 4 20mA QCL5 Max Min Max Min G WH BN inst m_03 SC BP it en fr de es pt nl pl el tr 229...
Страница 234: ...22 INST G_11_B SC 7 6 5 4 3 2 1 13 8 11 12 2 10 11 2 14 15 it en fr de es pt nl pl el tr 234...
Страница 235: ...23 INST G_12_B SC 1 2 7 15 14 6 5 4 3 8 9 2 10 11 12 18 13 it en fr de es pt nl pl el tr 235...
Страница 236: ...24 INST G_13_B SC 2 1 13 8 11 12 2 10 11 2 14 15 16 11 17 it en fr de es pt nl pl el tr 236...
Страница 237: ...25 13 15 14 INST G_14_B SC 8 9 2 1 2 10 11 12 18 17 16 11 it en fr de es pt nl pl el tr 237...
Страница 238: ...26 INST G_06_B SC 3 9 6 2 4 1 6 QCL5 5 8 2 2 2 1 m B 10 m 3 m A 7 it en fr de es pt nl pl el tr 238...
Страница 240: ...28 INST G_08_B SC 3 9 6 2 4 1 6 QCL5 5 8 2 2 2 1 m B 10 m 3 m A 7 it en fr de es pt nl pl el tr 240...
Страница 243: ......