The Auto-test of pump 1 has failed. The test is
stopped due to intervention of the membrane
pressure switch connected to the D IN PROG
(c38=1). The pressure in delivery side achieves
the setting of the pressure switch.
Causes/solutions
•
The pump (impeller or diffuser) is damaged.
Contact the technical assistance service.
•
The motor pump 1 doesn’t run:
o
It is damaged and must be replaced.
Contact the technical assistance service.
o
The thermal protector inside the motor
is faulty or broken.
o
The capacitor is damaged.
N°
Description
Reset
A25
Auto-test pump 2 failed
Auto
Troubleshooting:
The Auto-test of pump 2 has failed. The test is
stopped due to intervention of the membrane
pressure switch connected to the D IN PROG
(c38=1). The pressure in delivery side achieves
the setting of the pressure switch.
Causes/solutions
•
The pump (impeller or diffuser) is damaged.
Contact the technical assistance service.
•
The motor doesn’t run:
o
It is damaged and must be replaced.
Contact the technical assistance ser-
vice.
o
The thermal protector inside the motor
is faulty or broken.
o
The capacitor is damaged.
N°
Description
Reset
A36
High pressure alarm
Auto
Troubleshooting:
The pressure value has reached the set value of
the high pressure switch P MAX.
All the pumps are stopped.
The alarm is excluded in manual mode.
Causes/solutions
•
The pressure has reached the set value of the
high pressure switch P MAX: check the pump
performance curve and the proper set point
(r07) or thresholds of the pumps (r11, r13).
•
If the alarm appears but the pressure value
does not reach the value of the pressure
switch P MAX:
o
The maximum pressure switch must be
replaced.
o
The cable of the pressure switch is
faulty or worn, replace it.
o
Check connection of the pressure
switch P MAX to the Q-SMART control
o
The pressure switch P MAX is dam-
aged, replace it.
N°
Description
Reset
A37
Minimum pressure alarm
Auto
Troubleshooting:
The pressure value has reached the set value of
the minimum pressure switch P MIN. LEDs (4), (6)
on.
All the pumps are stopped.
The alarm is excluded in manual mode.
Causes/solutions
•
The pressure has reached the set value of the
minimum pressure switch P MIN. Check the
pump performance curve and the proper set
point (r07) or thresholds of the pumps (r10,
r12).
•
If the alarm appears but the pressure value
has not reached the set value of the pressure
switch P MIN:
o
The pressure switch P MIN is damaged
and must be replaced.
o
The cable of the pressure switch is
faulty or worn, replace it.
o
Check connection of the pressure switch
P MIN to the Q-SMART control panel
terminal (refer to figures
•
The pump (impeller or diffuser) is damaged.
Contact the technical assistance service.
•
The motor doesn’t run:
o
It is damaged and must be replaced.
Contact the technical assistance ser-
vice.
o
The thermal protector inside the motor
is faulty or broken.
o
The capacitor is broken.
N°
Description
Reset
A38
Minimum pressure out of op-
eration range.
Auto
Troubleshooting:
Tripping of the protection against operation of the
pump below the minimum pressure. The signal
arrives from the minimum pressure switch con-
nected to the digital input D IN PROG (c38=1). If it
appears during normal operation instead of during
the auto-test phase, all the pumps are enabled in
order after the set delay time (t38) to restore the
pressure.
Causes/solutions
•
There is an alarm but the pumps are stopped:
o
The pressure switch is faulty or its cable
is damaged. Replace the pressure
switch or cable.
o
Incorrect setting of the pressure switch,
change it.
•
There is an alarm but the pumps are running:
o
The pressure switch is faulty or its cable
is damaged. Replace the pressure
switch or cable.
Содержание Lowara Q-smart
Страница 2: ......
Страница 239: ...el 239 Tab 1 4 4 1 o 30 mA RCD o 3 mm C F1 F2 12 gG 7 5 4 3 5 4 4 3 2 70 C 158 F 4 2 4...
Страница 255: ...el 255 A54 r54 t54 o o o Reset A55 r55 t55 c02 0 t55 c02 1 o o o Reset A56 5 30 5 30 c57...
Страница 266: ...el 266...
Страница 298: ...ru 298 2 3 4 3 4 1 4 4 1 o 30 o 3 C 12 A gG F1 F2 7 5 4 3 5 4 4 3 2 70 C 158 F 4 2 4...
Страница 326: ...ru 326 o sE 2 o bS 3 11 11 1 2 Q SMART 30 12 7 9 12 1 F1 F2...
Страница 327: ...ru 327...
Страница 347: ...347 Q SMART 30 RCD 12 7 9 12 1 on F1 F2...
Страница 351: ...it en fr de es pt nl pl el tr ru ar 351 5 INST QSMARTCAVI_G_22_A SC 2 3 4 5 6 1...