P215 RAMP 1
4 sec
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
This parameter adjusts the fast acceleration time, and it effects the control of the pump;
the ramp depends on the type of HYDROVAR and the type of pump.
HVL
Possible setting (sec)
Default setting (sec)
2.015 ÷ 2.040
1–250
4
3.015 ÷ 3.040
4.015 ÷ 4.040
3.055 ÷ 3.110
1–1000
8
4.055 ÷ 4.110
4.150 ÷ 4.220
1–1000
12
For more information, see
Example: P200 Ramp Settings
(page 102).
P220 RAMP 2
G
NOTICE:
• Fast running down time often causes overvoltage.
• Slow running down time often causes over-pressure.
P220 RAMP 2
4 sec
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
This parameter adjusts the fast deceleration time, and it effects the control of the pump;
the ramp depends on the type of HYDROVAR and the type of pump.
HVL
Possible setting (sec)
Default setting (sec)
2.015 ÷ 2.040
1–250
4
3.015 ÷ 3.040
4.015 ÷ 4.040
3.055 ÷ 3.110
1–1000
8
4.055 ÷ 4.110
4.150 ÷ 4.220
1–1000
12
For more information, see
Example: P200 Ramp Settings
(page 102).
P225 RAMP 3
G
NOTICE:
• Fast running up time can cause oscillation and overload.
• Slow running up time can cause a drop of the outgoing operating pressure, during
variation of the demand.
8 Programming
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual
59