P202 SOFTWARE
1.00
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
For details, see the table below.
Displayed value
Additional information
1.00
First Release 12/2015
P205 MAX.UNITS
G
Set the maximum number of units that operate simultaneously.
P205 MAX.UNITS
6
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Reasonable values are:
Value
MODE
1–8
Cascade Serial
2–6
Cascade Relay
P210 INVERTER
G
Select the HYDROVAR address for parameterization.
P210 INVERTER
All
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Possible settings are:
Setting
Description
All
All units in the group are programmed at the same time;
in any case all new settings are copied to all units.
1– 8
Used if one specific unit is programmed. Select that unit
(1– 8).
P215 RAMP 1
G
NOTICE:
• Fast running up time can cause errors (overload) during the startup.
• Slow running up time can cause a drop of the outgoing operating pressure.