P266 MOTOR NOM.VOLT.
230 V
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
Possible settings are:
HVL
Possible setting (V)
Default setting (V)
2.015 ÷ 2.040
208–240
230
3.015 ÷ 3.110
208–240
230
4.015 ÷ 4.220
380–460
400
P267 MOTOR NOM.FRQ.
Sets the motor nominal frequency, as reported in the motor nameplate
P267 MOTOR NOM.FRQ.
50.0 Hz
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P268 MOTOR NOM.CURR.
Sets the motor nominal current, as reported in the motor nameplate, according to
• the chosen motor connection
• the output voltage of the HYDROVAR
P268 MOTOR NOM.CURR.
7.5 A
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P269 MOTOR NOM.SPEED
Sets the motor nominal speed, as reported in the motor nameplate
P269 MOTOR NOM.SPEED
3000 rpm
Actual Value
Output Freq.
Left fct.
Up fct.
Down fct.
Right fct.
P270 MOTOR POLES
This parameter (possible setting 2 or 4) sets the number of motor poles (display showing,
for example, the following information)
8 Programming
64
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual