earth leakage current depends on various system configurations including RFI filtering,
screened motor cables, and frequency converter power.
EN/EC61800–5–1 (Power Drive System Product standard) requires special care if the
leakage current exceeds 3.5 mA. Earth grounding must be reinforced in one of the
following ways:
• Earth ground wire of at least 8 AWG or 10 mm
2
Cu (or 16mm2 Al).
• Two separate earth ground wires of the same cross sectional area.
See EN60364–5–54 section 543.7 for further information.
On HYDROVAR, the phase conductor and the corresponding protective earthing
conductor can be of the same cross-sectional area, provided they are made of the same
metal (because the cross-sectional area of the phase conductor is less than 16 mm
2
).
The cross-sectional area of every protective earthing conductor which does not form a
part of the supply cable or cable enclosure shall, in any case, be not less than:
• 2.5 mm
2
if mechanical protection is provided or
• 4 mm
2
if mechanical protection is not provided. For cord-connected equipment,
provisions shall be made so that the protective earthing conductor in the cord shall, in
the case of failure of the strain-relief mechanism, be the last conductor to be
interrupted.
6.2 Protection devices
Fuses and Circuit Breakers
• An electronically activated function within the frequency converter provides overload
protection in the motor. The overload calculates the level of increase to activate timing
for the trip (controller output stop) function. The higher the current draw, the quicker
the trip response. The overload provides Class 20 motor protection. See Warnings and
alarms for details on the trip function.
• Hydrovar must be provided with short-circuit and over-current protection to avoid
overheating of the cables in the installation. Input fusing and/or circuit breakers are
required to provide this protection. Fuses and Circuit Breakers must be provided by
the installer as part of installations.
• Use recommended fuses and/or circuit breakers on the supply side as protection in
case of component breakdown inside the adjustable frequency drive (first fault). Use of
recommended fuses and circuit breakers ensures possible damage to the adjustable
frequency drive is limited to damages inside the unit. For other circuit breaker types,
ensure that the energy into the adjustable frequency drive is equal to or lower than the
energy provided by recommended types.
• The fuses below are suitable for use on a circuit capable of delivering 100,000 Ams
(symmetrical), 480V maximum. With the proper fusing the adjustable frequency drive
Short Circuit Current Rating (SCCR) is 100,000 Ams.
Table 1: Recommended fuses and circuit breakers
Voltage
supply
HVL
Fuse
Circuit
breaker
UL
Non UL
Bussmann
Edison
Littelfuse
Ferraz-
Shawmut
Fuse
ABB
Type T
Type gG
MCB S200
1~ 230 VAC
2.015
JJN-20
TJN (20)
JLLN 20
A3T20
20
S201-C20
2.022
JJN-25
TJN (25)
JLLN 25
A3T25
25
S201-C25
2.030
JJN-35
TJN (35)
JLLN 35
A3T35
35
S201-C32
2.040
JJN-35
TJN (35
JLLN 35
A3T35
35
S201-C40
6 Electrical Installation
HVL 2.015-4.220 Installation, Operation, and Maintenance Manual
27