An error indication is given over terminal X2/1, X2/2 and X2/3 (changeover contact).
If no Error is active, the relay is switched on and terminals X2/2 and X2/3 are closed.
Attention If "AUTO - START ON" and "ERROR-RESET – ON" are programmed, the unit
can start again automatically after a power failure.
8.6
Additional Error signals:
ERROR 1
:
EEPROM-ERROR (corresponding data block malfunction)
ERROR 2
:
Security error / Software protection error
ERROR 4
:
Display unit / Push buttons error (e.g.: jammed key)
ERROR 5
:
EPROM-error
ERROR 6
:
Program error: Watchdog
error
ERROR 7
:
Program error:
Processor pulse error
ERROR 8
:
Program error:
invalid processor command
These ERROR signals can be reset by cutting off the power supply or pressing all three
buttons (
Ï
,
Ð
and
¾
) together for about 5 seconds.
If the error signal should appear again, contact customer service and provide a detailed
description of the error.
9
RS 485 - Interface
Standardised Bus-Interface for communication between the inverters (Hydrovar-
Smart
and/or
Hydrovar Drive heads) and/or an overruling external control system.
The data protocol complies with ISO 1745 for RS 485 interfaces and contains the following
configurations:
Transfer rate : 9600 Baud (1 Start bit, 8 Data, 1 Stop bit)
An interface inverter RS 232/RS 485 is necessary in case communication with a V24 interface
of a PC or another external control system is wanted.
All parameters can be approached via the standard interface. The inline structure of the
Hydrovar-
Smart
Drive head can be obtained upon request.
For further information see:
serial data transmission – RS485
HYDROVAR
-
Smar
t
– Protocol 120