37
7.28
Submenu for manual test run
S U B M E N U
TEST RUN man.
Press
¾
for about 3 seconds to enter the submenu
and the display changes to
7.28.1
Activate manual test run
TEST RUN man.
Ï
+
Ð
By simultaneously pressing
Ï
+
Ð
a test run will
be released.
The function and operation of the started manual test run is similar to the automatic
test run
Press
¾
on the Hydrovar-
Smart
to change to
7.28.2
Test Frequency
TEST-FREQUENCY
30.0 Hz
Frequency for manual and automatic test run.
Can be set from 6.0 Hz up to 70,0 Hz
Press
¾
on the Hydrovar-
Smart
to change to
To leave the submenu press the
¾
longer than 3 sec. to change to
S U B M E N U
TEST RUN man.
Press
¾
on the Hydrovar-
Smart
to change to
7.29
Submenu - Error
S U B ME N U
ERRORS
Press
¾
for about 3 seconds to enter the submenu
and the display changes to
7.29.1
Conveyor Limit
CONVEYOR-LIMIT
disabled
Disabled or adjustable between 0.00...SENSOR
RANGE. To disable the conveyor limit, press
Ð
till
“
disabled
” or “0 bar” is shown on the display.
An adjusted value >0 has to be reached till the programmed “DELAY TIME”.
Doesn’t this value be reached; the failure “VAL. RANGE CONTR.” will be indicated and
the pump stops.
Press
¾
on the Hydrovar-
Smart
to change to