30
7.21
Submenu Sequence control
S U B M E N U
Seq. Control
Programming of the Multipump Operation:
Up to four pumps can be connected using the integrated RS-485 interface, by connecting
the terminals /1, /2 and /3 of the terminal blocks X5 or X6 of each pump together).
However, the following additional programming must be carried out in the submenu:
Press
¾
for about 3 seconds to enter the submenu and the display changes to
7.21.1
Lift Value
ACTU. VALUE INC.
0.35 Bar
Adjustable between 0.0 to the pre-selected
Sensor range
Operation of the start of the slave pump:
1)
Pump 1 reaches ENABLE SEQ. CONTROL (maximum speed)
2)
Pressure falls and reaches the start-value of the 2
nd
pump
(= REQUIRED VALUE – ACTU. VALUE DEC.)
3)
Pump 2 is switched on automatically
4)
The required value is calculated new, after the start of the 2
nd
pump in the
following way!
New required value
= REQUIRED VALUE – ACTU. VALUE DEC. + ACU. VALUE INC.
Generally:
k ... Number of active pumps (k >1)
p = p
set
+ (k-1)*[lift value – fall value]
•
Lift value = Fall value
⇒
Pressure constant
when pumps switch on
•
Lift value > Fall value
⇒
Pressure rises
when lag-pump switches on
•
Lift value < Fall value
⇒
Pressure falls
when lag-pump switches on