in Eagle due to excessive downloading. There are two levels of resetting a logger, performing a full memory reset OR
clear historic data.
1.
Full Memory Reset.
ONLY VIA USB
. A full memory reset
clears historic data and any configured settings, which is
especially useful to ensure that the station is starting anew.
Before doing this, retrieve all program files from the file
control tab to use once the memory is reset. Once retrieved,
select the
Data Monitor
tab, highlight the
Status
table, find
the variable
FullMemReset
and enter the code
98765
. Once
entered, listen for the sounds of the logger resetting. Follow
the steps under 15.1 for sending the retrieved program back
to the Ai1. This must only be performed via the USB connection. If this is performed over the cellular
connection, it will not be possible to reconnect to the station as the Pakbus Router settings are also cleared.
2.
Clear Historic Data. This clears data from specific data tables.
Using DevConfig, under Data Monitor tab, highlight each table
(excluding Public and Status which are not historic data tables)
and select the Reset Table button at the bottom of the
window, selecting yes to confirm.