25
Current (A)
185
370
556
741
926
Fixation torque force (lb-in)
60
60
60
60
60
Screw size
M8
For
X90-ENC10S
cabinet
Power rating
300KVA 350KVA 400KVA 450KVA 500KVA
Current (A)
793
926
1058
1190
1323
Fixation torque force (lb-in)
60
60
60
60
60
Screw size
M10
Power rating
420KVA 490KVA 560KVA 630KVA 700KVA
Current (A)
1111
1296
1481
1667
1852
Fixation torque force (lb-in)
60
60
60
60
60
Screw size
M10
NOTE: It is +/- 240VDC battery string
2.11 Wiring
WARNING:
⚫
Before connecting any wire, make sure the AC input and battery power is completely turned
off.
⚫
Make sure the breakers, Main Breaker (Q1), Maintenance Breaker (Q2), Output Breaker (Q3)
and battery breaker are all in the
OFF
position.
⚫
Make sure the Maintenance Bypass Switch is in UPS position.
Содержание X90-5S
Страница 17: ...15 X90 ENC5S...
Страница 18: ...16 X90 SMB350...
Страница 19: ...17 X90 ENC10S X90 SMB700 Figure 2 13 Terminal Blocks...
Страница 20: ...18 2 7 3 EMI solution To meet EMI requirements please add EMI core as Figure 2 14 Figure 2 14 EMI core...