250kVA/250kW
301
300kVA/300kW
361
350kVA/350kW
421
400kVA/400kW
481
450kVA/450kW
541
500kVA/500kW
601
Note:
1. Factory setting is 480V
660
8.7 Electrical Characteristics (Bypass Mains Input)
Table 8-7
: Bypass mains input
Rated power (kVA)
Unit
5
0 ~ 700
Rated AC voltage(1)
Vac 480 (three-phase three -wire, L-L, without neutral)
Overload
%
105%~110% for 60min
110%~125% for 10min
126%~150% for 1min
>150% for 200ms
Upstream protection, bypass
line
N/A Circuit breaker, rated up to 100% of nominal output
current.
Frequency
Hz
50/60 Auto Selectable
Transfer time (between bypass
and inverter)
ms
Inverter <->Bypass 0ms
Inverter <->
ECO ≤10ms
Bypass voltage tolerance
%Vac Upper limit: +10, default: +10
Lower limit: -10, -15, -20 default: -20
TBD
Frequency Range
Hz
+/- 1Hz, +/- 2Hz, +/- 4Hz (default: 4Hz)
Note
:
1. Factory setting is 480V