61
This delay time will start counting when the
CONTROL-Shutdown Restore command is executed.
System Restore Time
Set system restore time (0~9999min)
⚫
1 min (Default)
This delay time will start counting after shutdown time is
elapsed when the CONTROL-Shutdown Restore
command is executed.
Power rating
setting
--
Set power rating value per module
⚫
50kVA
⚫
70KVA
Redundancy --
Set total power and redundancy
Redundancy: the QTY of redundant power module
MUST be set after UPS installation or the QTY of
Power Module is changed
CT Ratio
Setting
--
Enable(Default)
Change current transformer Ratio Setting
4.2.6.3 Setup-Battery Screen
The Setup-Battery screen and setting list as shown in Figure 4-17 and table 4-9. Battery setting
can be set only when UPS is operated in standby mode. If it
’
s not in standby mode, the warning
screen will appear as shown in Figure 4-16.
Figure 4-17 Setup-Battery Screen
Battery setting can be set only when UPS is operating in standby mode. If it
’
s not in standby mode,
the warning screen will appear as shown in Figure 4-23. See Setup-Battery setting list in
Table
Table 4-9
: Setup-Battery setting list
Setting Item
Sub Item
Explanation
Nominal
Battery Voltage
--
Set battery nominal voltage
⚫
16x12V (Default)
⚫
18x12V
⚫
20x12V
MUST be set after UPS installation
Battery
Capacity in Ah
--
Set battery capacity. (0~999)
⚫
9Ah (Default)
MUST be set after UPS installation or Battery