6
TABLE 1-1
Line Amperes
Disconnect Switch
Fuse Size Amps
000.0 - 02.5
30A
05
003.0 - 04.5
30A
07
005.0 - 07.5
30A
10
008.0 - 11.0
30A
15
011.5 - 15.5
30A
20
016.0 - 18.0
30A
25
018.5 - 22.0
30A
30
022.5 - 27.0
60A
35
027.5 - 32.0
60A
40
032.5 - 40.0
60A
50
040.5 - 48.0
60A
60
048.5 - 64.0
80A
80
065.0 - 80.0
100A
100
081.0 - 95.0
125A
125
096.0 - 125.0
150A
150
1.4. AC Service Requirements
Follow local code requirements if they are different than the instructions in this manual. Refer to Table 1-1, to
determine the correct ratings for the AC cable, AC fuses, and AC service disconnect switch for the line
amperes as listed on the nameplate of the charger for the available AC voltage.
“CAUTION” – Risk of fire. Use only on circuits provided with 30 amperes branch circuit protection in
accordance with the National Electrical Code, NFPA70.
For voltages up to 240, use a 240 volt disconnect switch.
For voltages greater than 240 to 600, use a 600 volt disconnect switch.
Three conductors and ground wire required for three-phase
1.5. Connecting AC Service to the Charger
Three-Phase Models
Connect the AC service to the L1, L2 and L3 terminals located on the AC connection block.
1.6 Grounding the Charger
The charger must be grounded to the AC system ground for personnel safety.
The green ground wire in the AC input wiring must be connected to the charger ground stud identified by a
green dot and ground symbol.
1.7 Battery Connector and Charging Cable
Verify that the connectors on both the battery and the charger are attached so that the positive
output terminal of the charger is connected to the positive battery terminal.
CAUTION:
If the polarity is reversed, the DC fuse will blow.
If in doubt, check the polarity with a DC voltmeter.
Содержание HIGH FREQUENCY Series
Страница 1: ...High Frequency Battery Charger Installation and Operation Manual ...
Страница 16: ...16 ...
Страница 17: ...17 ...