Xtreme Power Conversion Corporation
E90 Service Manual
Page 56
Uninterruptible Power Supply
Press the Scroll key to highlight Battery and press the Enter key to enter the Setting-Battery window as shown
below.
Setting-Battery: press the Enter key to enter item and confirm value, press the Scroll key to change the value.
The following parameters can be adjusted:
Setting-Battery
Range
Default
Number1
20
20
Capacity2
7 - 2000
9AH
Boost Charge
Enable or disable
Enable
Group3
1-19
1
V-Boost
2.30-2.40, step is 0.01V
2.30 vpc
V-Float
2.20-2.29, step is 0.01V
2.27 vpc
V-EOD
1.60-1.90V
1.67 vpc
I-Maxcharge4
1-20A
Capacity x Group x .15
1. Number is the number of batteries per string
2. Capacity is the Amp-Hour rating of the batteries per string
3. Group is the number of strings of batteries
4. I-Maxcharge is the maximum charger current. Setting this above 15A on the E90-10kVA increases the input
current rating and requires an input circuit for 45A