Xtreme Power Conversion Corporation
E90 Service Manual
Page 55
Uninterruptible Power Supply
Press the Scroll key to highlight Bypass and press the Enter key to enter the Setting-Bypass window as shown
below.
Setting-Bypass: press the Enter key to enter item and confirm value, press the Scroll key to change the value.
The following parameters can be adjusted:
Setting-Bypass
Range
Default
Upper Limit
10%, 15%, 20%, 25%
25% VAC
Lower Limit
-10%, -20%, -30%, -40%
-40% VAC
F_Range
1%, 2%, 4%, 5%, 10%
10% HZ