Uninterruptible Power Supply
Setting-System: press the Enter key to enter item and confirm value, press the Scroll key to change the value.
The following parameters can be adjusted:
Setting-System
Range
Default
Working Mode
Normal, Parallel, ECO
ECO1
V Output Grade2
120 or 127
120
F Output Grade3
50 or 60
60
F mode
CVCF or Non-CVCF
Non-CVCF
Test type
OFF, 10s, 10min or EOD
Off
Test Cycle
1~30 days
30 days
Equipment ID4
1 - 15
1
Temp. Sensor SW
ON or OFF5
Off
1) Factory default setting for Working Mode is ECO. To disable ECO, reprogram Working Mode to Normal or
Parallel.
2) Must be in static bypass to change
3) If not in static bypass, output will drop load
4) This is the MODBUS device address used for RS232 & RS485 communication ports.
a. Press Scroll key to set the address.
b. When battery temperature sensor is open, choose ID 1~10 & 13~15
c. If UPS is set for parallel mode and device address <= parallel quantity, device address = parallel ID
d. Press “ON” to exit the device address setting and save the device address setting value and parallel ID setting.
e. Note: Under single UPS mode, until this device address setting save and exit, single UPS setting is done.
5) OFF turns off the sensor switch, ON turns on the sensor switch and send query command to sensor with
address 11 and 12 every second.