Detector Access
To gain access to the interior of the detector, first disconnect the power supply then remove the front cover. It
is secured by two screws underneath and hinged at the top, allowing complete removal. If the beacon option is
fitted, a cable-loom is attached; this may be unplugged at either end, but it may be easier to detach/reattach
the plug connecting to the main unit.
To access the Fault Relay and other I/O Module connections, the front panel must be dropped down by
loosening the two knurled screw fixings at either side.
Knock-out cable entry points are provided at the top and left-hand side of the metal back box. Where the field
wiring to the unit is not via conduit tubing, strain-relief type cable glands of a suitable size to fit the 25 mm
diameter holes must be fitted to all used cable entry holes. These cable glands shall be fitted so as to provide
strain relief and ensure that the protective earth connection (where used) is the last conductor to take any
strain.
External Power Supply Connection
VFT-15 detectors are powered by an external 24 VDC power supply.
The power supply cable cores should be fitted individually with ferrite cores, close to the cable gland inside the
equipment case. To fit the cables with the ferrite cores, insert the 24V and 0V conductors through the ferrite
cores and wrap around once to provide maximum effectiveness.
B
A
C
Legend
A
Power Supply Cables
B
Two Turns
C
Ferrite Core
Figure 3-2: Ferrite Core
Connect the 24 VDC power supply to the 5-way connector (CN2) on the I/O board under the control panel as
shown in Figure 3-3.
1. External Power
Supply
2. No Connection
3. Link
Figure 3-3: 24 VDC connection for VFT Detectors
The MAINS/BAT terminal must be linked to 0V. Failure to do so may result in a Mains Fault. The VBAT and
BATT TEST terminals should be left unconnected.
Ensure that in the Configuration menu, the STANDBY parameter is set to 0. For more information about
Configuration mode, refer to Section 5.3.4.
For use in UL/ULC Fire Alarm Application, refer to Appendix F.
Grounding and Fuse Protection
An M5 chassis earthing stud is provided for the grounding of the unit using a suitable gauge of wire or earth
braiding (0.75 mm² (0.03 in²) minimum) to a primary earth point (i.e. copper water pipe or an earth-stake etc.).
This chassis earth should be connected on all DC powered installations.
Содержание VESDA VFT-15
Страница 2: ......
Страница 6: ...VESDA VFT 15 Product Guide VESDA by Xtralis iv www xtralis com This page is intentionally left blank ...
Страница 8: ...VESDA VFT 15 Product Guide VESDA by Xtralis 2 www xtralis com This page is intentionally left blank ...
Страница 10: ...VESDA VFT 15 Product Guide VESDA by Xtralis 4 www xtralis com This page is intentionally left blank ...
Страница 16: ...VESDA VFT 15 Product Guide VESDA by Xtralis 10 www xtralis com This page is intentionally left blank ...
Страница 28: ...VESDA VFT 15 Product Guide VESDA by Xtralis 22 www xtralis com This page is intentionally left blank ...
Страница 46: ...VESDA VFT 15 Product Guide VESDA by Xtralis 40 www xtralis com This page is intentionally left blank ...
Страница 51: ...VESDA by Xtralis VESDA VFT 15 Product Guide www xtralis com 45 A Display Panel Navigation ...
Страница 52: ...VESDA VFT 15 Product Guide VESDA by Xtralis 46 www xtralis com This page is intentionally left blank ...
Страница 68: ...VESDA VFT 15 Product Guide VESDA by Xtralis 62 www xtralis com This page is intentionally left blank ...