VESDA VFT-15 Product Guide
VESDA by Xtralis
26
www.xtralis.com
Table 5-3: Engineering Parameters and Values
Parameter
Value
Description
VERSION
*.**
Version of Software in the processor module in the Main Unit. The software
can be upgraded using a PC and a special interconnect lead.
BUILD NO
*.**
Reference to specific software build.
GENERAL
FAULT
*.**
Fault list that generates fault number codes.
DETFLOW
**.*%
Sample flow through the detector. This measurement may be
enabled/disabled under Configuration.
FLOWnn
**.*%
Measurements of Sample flow rates for each sector. The number will vary
depending on the number of actual sectors sampled. The flow rates should
be normalized to 100% at installation. High pressure systems measure
pressure for each sampled sector.
BATTERY
**.*V
Measurement of backup battery voltage. Applies to internal power supply
units only.
OBS/M or
OBSC/FT
*.**%
Obscuration value in meters or feet. This is the same as the normal display.
To change from metric to imperial see Section 5.3.8.
REFDENS
*.**%
For special applications only.
MODn
1 to 5
Shows the module types that are fitted. These are read directly from the
Modules.
5.3.4
CONFIGURE: Configuration Mode
Minimum Access Code Required:
Level 1
The VFT-15 detector uses many configuration parameters, and is shipped with factory default values. The
Configuration Mode allows changes to be made to these parameters. Below is a list of user definable
parameters, and their Factory Default values. The Parameter
UP
and
DOWN
buttons (Isolate and Scan)
navigate through the list; the Value
UP
and
DOWN
buttons (Accept and Reset) change the value. The
ENTER
button (Sounder Silence) saves the new value, and moves to the next parameter.
Display Panel
Shorthand
Parameter
Range
Factory Default
OPCODE
Operator Function Access Code
0 to 999
0
ENDSCTR
End Sector (number of sectors used)
1 - 15
15
DENSLOG
Log of density change
0.01 to 20.00
0.02
F2LTCH
Fire 2 Latch
0 or 1
1
F1LTCH
Fire 1 Latch
0 or 1
1
ACTLTCH
Action Latch
0 or 1
1
ALTLTCH
Alert Latch
0 or 1
1
TRCLTCH
Trace Latch
0 or 1
1
FLTLTCH
Fault Latch
0 or 1
1
TRCRLY
Trace Relay 1
0 or 1
0
REFCOMP
Not Used (Leave at default setting)
0.000-2.000
0.05
REFDEL
Not Used (Leave at default setting)
5 to 60s
15s
FLOWLOG
Log of flow change
5.0 to 200.0
5.0
FLOWDEL
Flow Fault Delay
1 to 100s
5s
FLOWHI2
Flow High 2 Limit
105 to 200%
130%
FLOWHI1
Flow High 1 Limit
105 to 200%
120%
Table 5-4: Configuration Mode Parameters and Values
Содержание VESDA VFT-15
Страница 2: ......
Страница 6: ...VESDA VFT 15 Product Guide VESDA by Xtralis iv www xtralis com This page is intentionally left blank ...
Страница 8: ...VESDA VFT 15 Product Guide VESDA by Xtralis 2 www xtralis com This page is intentionally left blank ...
Страница 10: ...VESDA VFT 15 Product Guide VESDA by Xtralis 4 www xtralis com This page is intentionally left blank ...
Страница 16: ...VESDA VFT 15 Product Guide VESDA by Xtralis 10 www xtralis com This page is intentionally left blank ...
Страница 28: ...VESDA VFT 15 Product Guide VESDA by Xtralis 22 www xtralis com This page is intentionally left blank ...
Страница 46: ...VESDA VFT 15 Product Guide VESDA by Xtralis 40 www xtralis com This page is intentionally left blank ...
Страница 51: ...VESDA by Xtralis VESDA VFT 15 Product Guide www xtralis com 45 A Display Panel Navigation ...
Страница 52: ...VESDA VFT 15 Product Guide VESDA by Xtralis 46 www xtralis com This page is intentionally left blank ...
Страница 68: ...VESDA VFT 15 Product Guide VESDA by Xtralis 62 www xtralis com This page is intentionally left blank ...