VESDA by Xtralis
VESDA VFT-15 Product Guide
www.xtralis.com
63
F
UL/ULC wiring requirements for Fire Alarm
connection application
Figure F-1: ULC input and output requirements
1. 24 VDC input power applied to terminals 1 & 2 of CN2 as shown in item A above. 24 VDC supply shall
be a ULC-527 Listed Fire Alarm Control Panel or ULC-527 Listed power supply.
2. For connection to Analog addressable systems - monitoring of Alarm and Fault relay outputs are to be
connected as item C above (as a minimum). Optionally, there are an additional 3 relay outputs
corresponding to thresholds - Alert, Action and Fire 2 which can be monitored also. Additional
addressable contact monitoring devices would be used to monitor those output contacts as needed.
3. For Conventional Initiating device circuits – wiring of alarm and fault contacts shall be wired as shown
in item C above (as a minimum. Optionally there are 3 additional thresholds available (Alert, Action &
Fire 2) which can be monitored also. These would require the use of additional Initiating circuits from
the conventional control panel.
4. Additionally in either case above (Addressable or conventional interfaces) a remote reset input is
required to reset latched Alarm and Fault conditions on the unit. An external reset device would be
connected between CN3 & CN4 terminals as shown in item B above. This input will reset when the fire
alarm control panel is reset clearing all latched Faults and Alarms.
5. Installation of detectors shall meet all applicable requirements of the following:
a. Standard for the Installation of Fire Alarm System - CAN/ULC-S524
b. National Building Code of Canada.
c. National Fire Code of Canada
CN2: DC Supply
1
24 VDC in
Requires 16 x 0.25-15 A (18 AWG) cable (0.75mm
2
minimum IEC60227 H05
W-F/H05 WH2-F2 for EC).
Note:
Link Pin 2 (0 V) and Pin 5 (MAINS/BAT). Refer to page 13 for
further details.
2
0 VDC in
3
N/C
4
N/C
5
Mains/Battery
Table F-1: Connections for i602 I/O Board
CN3: Auxiliary Supply Output Interface
1
0 VDC
Requires 7 x 0.2 - 6 A (24 AWG) cable (1 A maximum load).
2
24 VDC
CN4: Remote Reset Interface
1
- input
Opto isolated input. 24 VDC low current signal.
2
+ input
Содержание VESDA VFT-15
Страница 2: ......
Страница 6: ...VESDA VFT 15 Product Guide VESDA by Xtralis iv www xtralis com This page is intentionally left blank ...
Страница 8: ...VESDA VFT 15 Product Guide VESDA by Xtralis 2 www xtralis com This page is intentionally left blank ...
Страница 10: ...VESDA VFT 15 Product Guide VESDA by Xtralis 4 www xtralis com This page is intentionally left blank ...
Страница 16: ...VESDA VFT 15 Product Guide VESDA by Xtralis 10 www xtralis com This page is intentionally left blank ...
Страница 28: ...VESDA VFT 15 Product Guide VESDA by Xtralis 22 www xtralis com This page is intentionally left blank ...
Страница 46: ...VESDA VFT 15 Product Guide VESDA by Xtralis 40 www xtralis com This page is intentionally left blank ...
Страница 51: ...VESDA by Xtralis VESDA VFT 15 Product Guide www xtralis com 45 A Display Panel Navigation ...
Страница 52: ...VESDA VFT 15 Product Guide VESDA by Xtralis 46 www xtralis com This page is intentionally left blank ...
Страница 68: ...VESDA VFT 15 Product Guide VESDA by Xtralis 62 www xtralis com This page is intentionally left blank ...