Chapter 2 Installing and Operating
2
Use flexible hose of appropriate size to connect the condensate outlet (Fig 2-31) to drainage
system, the height of the drainage shall be lower than that of the outlet.
The humidifier shall be connected to purified water mains with stable pressure of 1 bar ± 0.2 bar.
The conductivity of the water shall be no more than 10 µs/cm. Use ¼” PU pneumatic hose to
connect the humidifier inlet to a purified water source.
The USB is used to update software version, update temperature and humidity data for PC
processing. Use Ethernet interface for internet access and remote control or monitoring.
The minimum distance away from the back of the equipment to the wall, furniture or other
installations shall be 300mm!
Voltage, frequency and current for power supply must meet the requirements as designated
on the nameplate! Use power socket matching the power plug of the equipment. Hot
line(L)and neutral line(N)for single phase equipment must not be reversed!
Socket for power supply must be equipped with protective ground (PE) to prevent against
hazard of possible electric shock.
2.2.3 Humidifier
Fig 3 Humidifier
40 Piezoelectric element module
41 Water supply float valve
56 Low level switch
237 Humidifier cover