02/99
21
REVISE SETPOINTS
Depending on parameters changes in SET-UP/BASICS, the user must consult all the parameters defined in SET-
UP/SET-POINTS.
RPM OVERSPEED SHUTDN
The engine speed is above the preset threshold. The engine will shut down immediately.
RPM v FREQUENCY ERRO
This message indicates that there is a conflict between the engine speed and the alternator speed. This means that
the number of teeth (parameter in BASICS) is incorrect.
SHUTDOWNS BYPASS ON !
This message indicates that most of the safety devices have been configured as alarms.
STOP BUTTON PRESSED
This message indicates that the red button STOP on Progress has been activated, leading to immediate engine shut-
down.
SYNCHRONIZER TIME OUT
This message indicates that the synchronisation delay assigned to the genset has been exceeded.
UNEXPECTED BUS VOLTS
This message indicates that voltage is available on the bus while logically it should not be.
VOLTAGE NOT BUILT
This message indicates that the alternator voltage has not been stabilised, even after a preset period.
SET-UP/OPTION
Generic Paralleling
Mains
Cogeneration
Paralleling
PARAMETERS
Configuration
System
Stand-By ATS
Mode (resell)
Start
Configuration # 1
0
0
0
0
0
Configuration # 2
0
0
1
0
0
Configuration # 3
0
1
0
0
0 or 1
Configuration # 4
0
1
0
1
0
Configuration # 5
0
1
1
0
0
Configuration # 6
0
1
1
1
0
V – STARTING AND STOPPING THE GENSET(S)
DEPENDING ON THE CONFIGURATION
To identify your equipment configuration, consult the table below :