background image

16

02/99

Ramp +kVAr/Sec :
Value in kVAr which is imposed on the generator during load transfer phases from the mains to the genset or bet-
ween gensets. Adjustment kVAr by kVAr is possible.

Ramp -kVAr/Sec :
Value in kVAr which is imposed on the generator during load transfer phases from the genset to the mains or bet-
ween gensets. Adjustment kVAr by kVAr is possible.

kW Quota ++ :
Value, on external request, of power in kW/sec which is imposed on the generator.

kW Quota -- :
Value, on external request, of power in kW/sec which is imposed on the generator.

In # 00 >>  kW Quota ++ :
By replacing In#00 by 06, 08, 09 or 12, and if it has not been already allocated, the chosen input enables to make a
dynamic check of the power (kW).

In # 00 >>  kW Quota -- :
By replacing In#00 by 06, 08, 09 or 12, and if it has not been already allocated, the chosen input enables to make a
dynamic check of the power (kW).

kVAr Quota ++ :
Value, on an external request, of power in kVAr/sec which is imposed on the generator.

kVAr Quota --  :
Value, on an external request, of power in kVAr/sec which is imposed on the generator.

In # 00 >>  kVAr Quota ++ :
By replacing In#00 by 06, 08, 09 or 12, and if it has not already been allocated, the chosen input enables to make a
dynamic check of the power (kVAr).

In # 00 >>  kVAr Quota -- :
By replacing In#00 by 06, 08, 09 or 12, and if it has not already been allocated, the chosen input enables to make a
dynamic check of the power (kVAr).

% kW / Xre >> R # 1 On  :
Not used.

% kW / Xre >> R # 1 Off :
Not used.

+ % kW / Xre >> Start :
Value expressed as a percentage of the genset power that allows the next genset to start-up in a sequence (only
used in configuration #3 with automatic program "Parall Auto Start"). See "Standard applications".
+ % kW / Xre >> Stop :
Value expressed as a percentage of the genset power that allows the next genset to shut down in a sequence (only
used in configuration #3 with automatic program "Parall Auto Start"). See "Standard applications".
Exclude Net IDs :
Allows the exclusion from the network of a certain number of gensets according to the ID Nos (number of gensets).

In # 06 Excludes :
Option at (1) enables to isolate a genset from the RS 485 network by activating input In#6.
Option at (0) enables to use input In#6 in a standard way.

In # 08 Excludes :
Option at (1) enables to isolate a genset from the RS 485 network by activating input In#8.
Option at (0) enables to use input In#8 in a standard way.

In # 09 Excludes :
Option at (1) enables to isolate a genset from the RS 485 network by activating input In#9.
Option at (0) enables to use input In#9 in a standard way.

In # 12 Excludes :
Option at (1) enables to isolate a genset from the RS 485 network by activating input In#12.
Option at (0) enables to use input In#12 in a standard way.

C - OPTIONS - IDENTIFYING BY  {.....}

Write Protect...!? :
Selection (0) : all parameters defined in SET-UP are accessible to read and to modify.
Selection (1) : all parameters defined in SET-UP are only accessible to read.

Http://www.xinke-hk.com

ShenZhen XinKe power equipment Co .Ltd

Содержание A400

Страница 1: ...pr ro od du ui it ts s e en ng ga ag ge en nt t n no ot tr re e S So oc ci ié ét té é à à s se e r ré és se er rv ve er r l le e d dr ro oi it t d de e t to ou ut te es s m mo od di if fi ic ca at ti io on ns s s sa an ns s p pr ré éa av vi is s T To ou us s d dr ro oi it ts s d de e m mo od di if fi ic ca at ti io on ns s d de es s p pr ré és se en nt ts s m ma an nu ue el ls s r ré és se er rv v...

Страница 2: ...protected Compulsory stacking point Water based fire extinguishers forbidden A 02 99 Due to on going research in our design offices and the continuous improvement of our products our Company reserves the right to make changes without prior notice All rights to change the contents of the current manuals reserved Reproduction and translation even partial forbidden without special authorisation Desig...

Страница 3: ... remote in Version IV V 13 MICS Progress 14 4 position function switch 15 Oil temperature gauge 16 Battery ammeter gauge 17 Shutdown extractor light 18 MDEC synthesis alarm light 19 Lack of water preheating light 20 Retention tank warning light 21 Test lamps push button Progress can be factory configured in several ways Any further changes will have to be submitted to our company prior consent A H...

Страница 4: ...ing mode is used to check the proper off load operation of the genset TEST For test purposes this operating mode enables you to check the automatic start up facility as it simulates a mains failure The genset starts automatically and delivers power to the installation A DESCRIPTION The control racks are fitted with various standard or optional instruments and gauges Depending on the options select...

Страница 5: ...e in the engine lubricating system Indicates the coolant temperature in the engi ne Indicates the voltage in Volts of the starting battery ies Indicates the amount of fuel in the tank This totals the genset running hours as soon as it starts To be pushed in the event of an accident or problem it will immediately stop the genera ting set from functioning It must be reset when the genset is returned...

Страница 6: ...unction genset genset or genset mains Paralleling function genset genset or gen set mains Load distribution function between gensets The screen allows you to view all alarms and faults the genset operating states various parameters which can be modified with access code The keypad ensures modification of the follo wing delays set up thresholds genset general parameters basics access to the various...

Страница 7: ...lt lamp Restarting the genset will not be possible until the fault has been RESET In a window the Left and Right arrows enable access to the various options offered see next page for list of screens Pressing this key enables access to the higher level screen see next page for list of screens Pressing this key enables 1 Access to the value of a parameter 2 Validation of a command or the value of a ...

Страница 8: ... 0 A 1 B S I W shutdown I Warning IN 1 16 In 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 N O N C Select Enter Esc Γ Battery Volts 23 8 MPU 1513 rpm 50 36 Hz kW Hours 00 001 234 HoursRun 000 150 10 Gen Volts Amps Hz Φ A 221 115 50 07 Φ B 222 117 kW Φ C 220 125 69 9 MAINS or BUS Mains Φ Α Frequency Hz 50 14 Voltage Vrms 223 Distorsion THD 0 1 SYNCscope Gen Φ A v Mains or BUS Φ A Freq Slip Hz 0 07 Phase Shift 11...

Страница 9: ...ion function switch Pressing Enter enables you to go from MAN OFF to OFF MAN and shuts down the genset after a cooling per iod Load GEN This function enables the genset to take the load The user password is required It leads to the automatic closure of the contactor The message OFF LOAD then appears OFF LOAD This function has the effect of opening the contactor 02 99 7 MODE AUTO TUE 22 37 Sets Run...

Страница 10: ...ction applies to the MICS Progress in configuration 3 production station no mains and when option Parall auto start is selected It enables the order in which the gensets must start to be dis played and modified The first line indicates the starting sequence example Genset No 2 then Genset No 1 then Genset No 3 The second line indicates the MICS Progress No on which the display is made The third li...

Страница 11: ...ncy in Hz Energy supplied in kWh stored Genset Hours Run stored MAINS or BUS This screen indicates Frequency in Hz Phase neutral voltage in Volts Total harmonic distortion depending on the value of mains control INS 0 or 1 the values measured come from the mains or bus GENERATOR Main panel to view the electric variables relating to the alterna tor ENGINE Battery Volts 23 8 MPU 1513 rpm 50 36 Hz kW...

Страница 12: ...ffective voltages in Volts Press Esc to return to the higher level menu Press Esc to return to the higher level menu Press Esc to return to the higher level menu Press Esc to return to the higher level menu Press Esc to return to the higher level menu SYNCSCOPE This screen gives information on the synchronisation status bet ween the genset between the genset and the bus or the genset and the mains...

Страница 13: ...l through use the arrows and To modify use and the keypad FACTORY This screen is available only after entry of the factory code It defines the factory set parameters SET UP DELAYS SET POINTS OPTIONS IN 1 16 BASICS FACTORY Select Enter Esc Γ DELAIS Set Overspeed 3 0 Gen OverVolts 1 0 Gen OverVolts 1 0 Gen OverVolts 1 0 SETPOINTS User Password 1 Crancking attempts 3 Overspeed RPM 1650 Crankstop RPM ...

Страница 14: ...reen REPORT to view faults and alarms 2 Direct access to screen OVERVIEW giving single voltage and current for each phase as well as frequency and total active power 3 Direct access to screen GEN ΦΦ giving the 3 single voltages the 3 phase to phase voltages and frequency 4 Direct access to screen POWER PF giving total active reactive apparent powers and power factor on each phase 5 Direct access t...

Страница 15: ...stability depending on the voltage configuration on V4 Standby On Delay after mains failure before the genset starts in automatic mode with control INS 1 Stanby Off Delay after mains return before load is removed from genset in automatic mode with control INS 1 Eng Preglow Delay for preheating of air intake glow plug s before start up Engine crank Time for starter to trigger period of one attempt ...

Страница 16: ...n 16 not activated time before the export quota in kVAr decreases R 1 Off On When option R 1 Trip kW Load is at 1 it is the time before relay 1 is excited R 1 On Off When option R 1 Trip kW Load is at 1 it is the time before relay 1 is de excited Parll Start When option Parall Auto Start is at 1 it is the delay assigned to the genset before its start up on a load increase Parll Stop When option Pa...

Страница 17: ...age for the rated speed Gov Volt Bias Phase shift authorised for the paralleling of V1 and V4 V1 genset phase 1 voltage V4 mains or bus phase 1 voltage SYNC Window V Voltage difference authorised for the paralleling of V1 and V4 V1 genset phase 1 voltage V4 mains or bus phase 1 voltage SYgain V 180 Value of off load synchronisation gain SYg V 180 Value of on load synchronisation gain SYstbl V Hz V...

Страница 18: ...a dynamic check of the power kVAr kW Xre R 1 On Not used kW Xre R 1 Off Not used kW Xre Start Value expressed as a percentage of the genset power that allows the next genset to start up in a sequence only used in configuration 3 with automatic program Parall Auto Start See Standard applications kW Xre Stop Value expressed as a percentage of the genset power that allows the next genset to shut down...

Страница 19: ...t down alarm GENCON low DC S W On sensing a low level of supply voltage 0 leads to engine shut down fault 1 does not lead to engine shut down alarm Generic configure Choosing this option allows to make specific applications which are not defined in the docu ment Standard Applications No 33502002401 Parallelin System The option configured at 1 enables the use of all synchronisation functions for pa...

Страница 20: ...les the use of alarm inputs for unused optional faults In 08 Aux Shutdn Enables the use of alarm inputs for unused optional faults In 09 Aux Shutdn Enables the use of alarm inputs for unused optional faults In 12 Aux Shutdn Enables the use of alarm inputs for unused optional faults D BASICS GENERAL PARAMETERS Controller ID No Progress ID between 1 and 8 A unique value must be allocated to each Pro...

Страница 21: ...GINE SHUT DOWN FAIL This message indicates that the fuel solenoid is not being supplied ENGINE SLOWCRANK This message indicates that the genset speed is below 60 rpm 2 seconds after the starter has been activated EXTERNAL OVERLOAD When input In 14 is activated this indicates an overload or a short circuit leading to the opening of the circuit breaker FREQENCYNOT BUILT This message indicates that t...

Страница 22: ...B1 When input In 11 is activated this indicates a low fuel level which does not lead to engine shut down alarm LOW OIL PRESS SHUTDN OB1 When input In 5 is activated this indicates a low oil pressure which leads to immediate engine shut down fault LOW OIL PRESS WARNIN OB1 When input In 6 is activated this indicates a low oil pressure which does not lead to engine shut down alarm LOW WATER LEVEL Whe...

Страница 23: ...mmediate engine shut down SYNCHRONIZER TIME OUT This message indicates that the synchronisation delay assigned to the genset has been exceeded UNEXPECTED BUS VOLTS This message indicates that voltage is available on the bus while logically it should not be VOLTAGE NOT BUILT This message indicates that the alternator voltage has not been stabilised even after a preset period SET UP OPTION Generic P...

Страница 24: ...iod An adjustable delay in menu SET UP DELAYS sets the time during which the genset will run manually Automatic operation To start in automatic mode the 4 position function switch must be moved to AUTO The genset is on stand by and Progress awaits a command to start This command comes from information V4 mains or bus mains failure or bus available or external information In both cases the genset s...

Страница 25: ...t the operating mode of the selected configuration consult the document no 335 02 002 401 This document shows in detail the operation of the various standard configurations applicable to the MICS Progress 02 99 23 Http www xinke hk com ShenZhen XinKe power equipment Co Ltd ...

Отзывы: