Motor contactors ? : The option at :
(0) : indicates that the power component(s) are controlled in a classic way (e.g. contactor).
(1) : indicates that the power component(s) are controlled by an electric motor with shut-off solenoid and open sole-
noid (motorized switch or motorized open-type breaker).
R # 1 Shunt/kw load :
(0) : relay R#1 is used to signal a fault.
(1) : relay R#1 is used for load control applications.
R # 2 Alarm/ Useable :
(0) : luminous alarm.
(1) : optional use.
K # 6 Engine/GEN on :
Output K#6 is supplied in the two following cases :
(0) : when the engine is running : speed 60 rpm or frequency 15 Hz.
(1): when the generator voltage is high, i.e. V1, V2 and V3 Gen Unvoltage.
K # 8 Delay/neutral : This option is only used in configuration #3 :
(0) : relay K#8 (IOB1 interface) is activated after relay K#7 (IOB1 interface) depending on the preset delay. Relay K#8
is deactivated at the same time as K#7.
(1) : Not used.
kW Drop=LoadSurge :
Not used.
Smooth Mains>>GEN ? :
Not used.
In # 06 Aux Shutdn ? :
Enables the use of alarm inputs for unused optional faults.
In # 08 Aux Shutdn ? :
Enables the use of alarm inputs for unused optional faults.
In # 09 Aux Shutdn ? :
Enables the use of alarm inputs for unused optional faults.
In # 12 Aux Shutdn ? :
Enables the use of alarm inputs for unused optional faults.
D - BASICS - GENERAL PARAMETERS
Controller ID No :
Progress ID, between 1 and 8. A unique value must be allocated to each Progress that is connected to the RS 485
communication bus (use in configuration #3 only).
Number of poles :
Number of pairs of rotor poles (always an even number).
PickUP Teeth :
Number of teeth on the flywheel. This value is used to calculate the engine rotation speed (for display).
CT Ratio :
Transformation ratio of the current transformers. For example, a 160 ratio corresponds to a 800A/5A current transfor-
mer.
Pt Ratio :
Transformation ratio of the potential transformers for use with average voltage. The minimum value to enter is 16.
Xap : Rated kVA :
The genset power expressed in kVA.
Xre : Rated kW :
The genset power expressed in kW.
Adj Sec/Week :
Real time clock adjustment specified in seconds per week.