Stoppin Max :
Time limit for closure of fuel solenoid to reach genset shut down conditions.
Alarm On Max :
Delay of R#3 relay activation (external audible alarm).
LubPump On :
Operating time of pre-lubricating pump.
LubPump Off :
Delay between 2 operations of the pre-lubricating pump..
LoadBreak >> Make :
ATS delay.
Contactor Delay :
Delay assigned to contactor between time of closure and return of information on Progress.
K # 7 On >> K # 8 On :
Use in configuration #3. Delay of closure which exists between commands K#7 and K#8 (outputs IOB1).
kW Quota ++ :
When Progress is in configuration #4 (mains paralleling) and In#16 not activated; time before the export quota in kW
increases.
kW Quota -- :
When Progress is in configuration #4 (mains paralleling) and In#16 not activated; time before the export quota in kW
decreases.
kVAr Quota ++ :
When Progress is in configuration #4 (mains paralleling) and In#16 not activated; time before the export quota in kVAr
increases.
kVAr Quota -- :
When Progress is in configuration #4 (mains paralleling) and In#16 not activated; time before the export quota in kVAr
decreases.
R # 1 Off >> On :
When option R#1 : Trip\kW Load is at 1, it is the time before relay #1 is excited.
R # 1 On >> Off :
When option R#1 : Trip\kW Load is at 1, it is the time before relay #1 is de-excited.
Parll Start :
When option Parall Auto Start is at 1, it is the delay assigned to the genset before its start-up on a load increase.
Parll Stop :
When option Parall Auto Start is at 1, it is the delay assigned to the genset before its shutdown on a load decrease.
LS Settling :
When option Parall Auto Start is at 1, it is the delay for 2 gensets to shut down after a significant decrease of load.
B - SET POINTS
User Password :
The user must enter a 4-digit password to change the operating mode or to change parameters.
Cranking Attempts :
Number of start-up attemps.
Overspeed RPM :
Overspeed threshold depending on the engine rating.
CrankStop RPM :
Threshold of starter throw out depending on the type of starter used.
Bat OvVoltage :
Threshold of battery overvoltage authorised.
Bat UnVoltage :
Threshold of battery undervoltage authorised.
GEN OvVoltage :
Threshold of overvoltage applied to phase/neutral voltage.