XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 36 of 36

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

TECHNICAL SPECIFICATION 

Part Nos. 

XFP501E/H, XFP501E/X

 

POWER SUPPLY SPECIFICATION

 

 
Mains supply (a.c.)                                                                                      230V 

 50/60Hz. Rated current 0.35A r.m.s 

Internal power supply                                                                               27Vd.c nominal (Ripple voltage 500mV) 
Maximum rated current                                                                           1.5A @ 230Va.c. 
Current specification                                                                                  I max. a = 210mA; I max. b = 1.1A; I min. = 40mA 
Maximum internal battery resistance                                                   Ri max. = 1.1

Ω

 

Supply and battery charger monitored for failure                            Yes 
Batteries monitored for disconnection and failure                            Yes 
Batteries protected against deep discharge                                        Yes 
Maximum battery size and type                                                             2 x 12V 3.2Ah VRLA type, connected in series. 

Use 2 x YUCEL 3.2-12 for LPCB approved systems.

 

Quiescent current drain (1 loop unloaded)                                         < 50mA 
Earth fault monitoring                                                                              Yes (any conductor) 
Temperature compensated charging                                                    Yes 

 
LOOP DRIVER SPECIFICATION

 

 
Number of loop drivers                                                                            1 
Line monitored for open and short circuit faults                               Yes 
On-board loop isolators with LED indication when active              Yes 
Auto-polling from each loop end                                                          Yes 
Maximum output current per loop                                                       500mA (Voltage: 25V minimum; 34V maximum) 
Maximum number of addressable devices                                          126 
Max. number of loop powered sounders per loop @ 10mA          40 
Number of programmable sounder groups                                        16 
Number of programmable output sets                                                16 
 

CONVENTIONAL SOUNDER CIRCUIT SPECIFICATION

 

 
Number of programmable circuits                                                        2 
End of line resistor value                                                                          6800 ohm 5% tolerance 0.25W

 

Line monitored for open and short circuit faults                               Yes 
Outputs fused at                                                                                         400mA. Protected by resettable overload circuit 
Output voltage                                                                                           19.5V minimum; 28V maximum 
Maximum number of sounders @ 20mA                                             40 
 

AUXILIARY OUTPUTS

 

 
Type                                                                                                               Relay voltage free single pole changeover 
Maximum switching current                                                                   1A 
Maximum switching voltage                                                                   30Vd.c. 
Relay 1 / Relay 2 / Relay 3                                                                         Programmed from cause and effect 
Fault                                                                                                               Active when no faults are present 
‘24V’ Aux. power output                                                                          19.5V minimum, 28V maximum.  Maximum current 100mA. Protected by resettable overload circuit. 
 

AUXILIARY INPUTS

 

 
Input 1                                                                                                           Connect to 0V to trigger, Max. input voltage 27V d.c (non-latching). Programmed from cause & effect 
Input 2                                                                                                           Connect to 0V to trigger, Max. input voltage 27V d.c (non-latching). Programmed from cause & effect 
 

FUSES

 (IEC - EN60127 Pt2) 

 
Primary fuse                                                                                                 T 1A H 230V 20mm ceramic

 

(T=Time Delay, H=High Breaking Current) 

Battery fuse                                                                                                  F 1.6A, 20mm ceramic 

(F = Fast)

 

 

PANEL INDICATORS AND CONTROLS

 

 
Control buttons                                                                                          Menu, More Information, Silence Internal Sounder, Control Panel Reset, Investigate, Resound 
Event scrolling and menu access buttons                                             Up

5

(1), Down

6

(3), Accept

4

(2), Escape

3

(4) 

Liquid crystal display                                                                                  Two lines x 40 characters, backlit 
Number of zonal LED indicators                                                             16 
Other LED indicators                                                                                  (General) Fire, Supply Present, Test, Accessed, General Disablement, Phased Evacuation, General 
                                                                                                                        Fault, Power Supply Fault, System Fault, Sounder Status, Delays Running. 

 

PHYSICAL

 

 
Dimensions of panel (W x H x D)                                                           380 x 235 x 90mm (plastic) 
Weight (without batteries)                                                                      1.8kg 
IP rating (to EN60529)                                                                               IP30 

 

CABLING REQUIREMENTS

 

 
Type of cable                                                                                               Fire resistant screened cable, minimum size 1mm

2

 

Maximum cable length per loop                                                            1km 
Connector blocks                                                                                        Plug-on type, largest acceptable conductor size, 1.5mm

2

 

Maximum allowable loop impedance (each conductor)                 20 ohm 
Maximum cable capacitance                                                                   .27µF 

 

NETWORK SPECIFICATION (OPTIONAL)

 

 
Connection                                                                                                   Via XFP761 network driver fitted in each networked main panel 
Maximum no of main panels per network                                         8 
Maximum no of repeaters per non-networked main panel           8 
Maximum cable length per network                                                    1km (main panel network); 500m (repeater network) 

 

PC/PRINTER INTERFACE

 

 
PC connection                                                                                              Via main panel RS232 molex connector (lead supplied in XFP507 upload/download software kit) 
Printer connection                                                                                      Not applicable 

 

OPERATING CONDITIONS

 

 
The enclosure is designed for indoor use only. The components are selected to operate within their specification when the environmental conditions 
outside the enclosure comply with class 3k5 of IEC 721-3-3. Temperature range: -10

o

C to +40

o

C. Maximum humidity: 95% non condensing.

CERTIFICATES 

(Certificates and DOPs are available for download on C-TEC’s website)

LPCB Cert No.: 176b

LPCB Reference Nos.: XFP501E/H (176b/05), XFP501E/X (176b/06)

DOP Nos.: DOP0000035 (XFP501E/H), DOP0000034 (XFP501E/X)

Tested to: EN54-2:1997 + A1:2006 & EN54-4:1997 + A1:2002 + A2:2006 CPR Certificate Nos: 0832-CPR-F1585 (XFP501E/H), 0832-CPR-F1586 (XFP501E/X)

Содержание XFP501E/H

Страница 1: ...XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL Single Loop 16 Zone Version Part Nos XFP501E X XFP501E H engineering manual Approved Document No DFU1200510 Rev 3...

Страница 2: ...Fitting the panel s NVM memory unlock link 18 A detailed description of the functions available at access level 19 33 Maintenance 34 Standby battery calculation guide 35 Technical specification 36 XF...

Страница 3: ...tem is commissioned and serviced in accordance with the laid down specification and national standards If in doubt please consult your supplier We recommend you read BS 5839 Part 1 Fire Detection and...

Страница 4: ...er or not it operates in day night mode which works as follows When there is an alarm in a zone programmed to operate in investigate mode the full alarm condition will occur after a delay It is possib...

Страница 5: ...irst fix installation to protect the electronics from damage Removing the lid and base PCBs Fig 1 Location of the panel s base PCBs and removal details 1 Take the panel out of its box and undo the two...

Страница 6: ...panel to ensure straightforward connection of the field wiring to the panel s terminals Drill centre points are provided in the panel base to aid drilling tools Cut out suitable holes in the panel us...

Страница 7: ...V V V HRC F F 1 1A 2 0 50 250 0 0 V V 0V V V V V HRC V 0V V 0 HR R V V 0V 1A 250 R 1A R THIS WAY UP CONN1 N L Mains Input CONN1 L Live BROWN N Neutral BLUE Earth GREEN YELLOW The incoming Mains earth...

Страница 8: ...o devices will lost since communication is from both ends of the loop but a loop integrity fault will be shown Note that a critical design issue with any analogue fire system is the combined effect of...

Страница 9: ...etaining screws are properly tightened before oper ation as they play an important part in the electrical safety and EMC immunity of the panel Fig 5 Typical analogue addressable loop connection GENERA...

Страница 10: ...inal block marked Auxiliary on the Main Control PCB as shown in Fig 7 right Remember to isolate the panel s Mains and battery backup supplies before making any connections If applicable i e in electri...

Страница 11: ...vided and can be used for supplying power to ancillary fire alarm equipment Installing the standby battery supply There is a risk of explosion if incorrect battery types or sizes are used Always repla...

Страница 12: ...interconnection of up to eight XFP main panels any mix of single loop 16 zone XFPs and 1 and 2 loop 32 zone XFPs Up to 1 km of cable may be fitted to an XFP main panel network Each networked XFP main...

Страница 13: ...allation where pertinent see cable types limitations page 3 A typical XFP main panel non redundant network A typical XFP repeater non redundant network SPUR WIRING NOT ALLOWED SPUR WIRING NOT ALLOWED...

Страница 14: ...rm is silenced Subsequent fire conditions will restart the General Fire indicator flashing until it is silenced again Fire Zones 1 16 One or more of these indicators will flash red in an alarm conditi...

Страница 15: ...nt settings etc serve as code input buttons to access levels 2 or 3 Accept 4 2 Dependent on the status of the panel these two buttons Escape 34 scroll horizontally through the panel s user menus escap...

Страница 16: ...the protocol of the panel etc Investigate any faults reported on the panel s display and take the necessary steps to correct them When all faults have been corrected carry out a loop learn as detaile...

Страница 17: ...LE DISABLE OUTPUTS ENABLE DISABLE RELAYS ENABLE DISABLE DEVICES ENABLE DISABLE FAULT RELAY ENABLE DISABLE OUTPUT DELAYS ENTER ACCESS LEVEL 2 DISPLAY FIRE EVENTS DISPLAY FAULT EVENTS DISPLAY DISABLEMEN...

Страница 18: ...de range of commissioning functions including auto loop learn device calibration and group zone assignment Gain access to a wide range of engineering test and fault finding functions Ascertain softwar...

Страница 19: ...level 3 menu press the Escape3button Display Zones In Test This function is only available if one or more zones are being tested If available press the Accept4button and a window similar to the one b...

Страница 20: ...T COMMS FUNCTION This function allows you to set the panel s RS485 comms to operate in Network or Repeater mode When selected press the Accept4button and a message similar to the one below will appear...

Страница 21: ...been programmed or if you want to program an existing system as if it were a new system press the Accept4button The following message will appear Press the Accept4button again and the panel will erase...

Страница 22: ...or group and press the Accept4button The device search will now continue until the next new device is found Note that I O units etc can only be assigned to output sets via the panel s programming too...

Страница 23: ...software tools must be used to assign them to output sets CALIBRATE DEVICES Daily calibration of the system s smoke and heat detectors to take into account environmental changes drift compensation fa...

Страница 24: ...licate address to check SET DAY NIGHT TIMES This function allows the user to alter the time the panel enters day building occupied and night building unoccupied mode WE RECOMMEND YOU DO NOT USE THIS F...

Страница 25: ...pre alarms etc and is normally used to tem porarily disable a zone of detectors call points in areas such as loading bays that are prone to nuisance triggering from vehicle fumes When selected press...

Страница 26: ...abled from reporting faults fires pre alarms etc and is normally used to temporarily disable detectors call points that are nuisance tripping When selected press the Accept4button and a window similar...

Страница 27: ...O unit is functioning correctly Addressable devices typically have three output chan nels 1 2 and 3 the functions of which depend upon its type please refer to the device manufac turers technical data...

Страница 28: ...groups 1 to 16 by altering its their state between Silenced Intermittent and Continuous When the TEST SOUNDER GROUP prompt appears press the Accept4button and the sounder group selection window will a...

Страница 29: ...ct the test to be carried out from either end of the loop or from both ends at the same time An example illustration of how this test may be carried out is shown below When the BLINK DETECTOR LEDs pro...

Страница 30: ...cepted the device s output bits sequence by pressing the Accept4 button the test will begin and the panel will display the device s current analogue values for example As the device is intensively pol...

Страница 31: ...o assert output channels 1 and 3 of the device being viewed press the More Information button You will be presented with a window similar to the one below In the case of detectors and manual call poin...

Страница 32: ...ng correctly Mis matched numbers i e 49191 40286 indicate that the panel s memory may be corrupt After five seconds the panel will return to the Engineering Functions submenu SHOW PSU STATS This funct...

Страница 33: ...upon the size of the loop and the number of items connected Press the Escape3 button to return to the Engineering Functions submenu SHOW DISCOVERY EEPROM This function allows the panel to interrogate...

Страница 34: ...tenance and installation regulations The Fire Alarm panel s standby batteries should be checked for integrity of the connections deposits indicating venting and a periodic load test with the Mains sup...

Страница 35: ...guideline the average quiescent current addressable devices is typically 0 00025A 250 A To obtain accurate figures consult the device manufacturers own specifications A The total alarm current of the...

Страница 36: ...tage 27V d c non latching Programmed from cause effect Input 2 Connect to 0V to trigger Max input voltage 27V d c non latching Programmed from cause effect FUSES IEC EN60127 Pt2 Primary fuse T 1A H 23...

Отзывы: