background image

ZONE 9

ZONE 10 ZONE 11

ZONE12

D45

SUPPLY

PRESENT

TEST

ACCESSED

GENERAL

DISABLEMENT

GENERAL

FAULT

PSU

FAULT

SYSTEM

FAULT

SOUNDER

STATUS

REMOVING THIS CIRCUIT
BOARD EXPOSES HAZARDOUS
VOLTAGES -  PLEASE REFER TO
INSTALLATION INSTRUCTIONS

WARNING

SENSITIVE TO STATIC
ELECTRICITY -  OBSERVE
PRECAUTIONS BEFORE
HANDLING

CAUTION  - RISK OF EXPLOSION IF
INCORRECT TYPE OF BATTERIES FITTED.
DISPOSE OF USED BATTERIES ACCORDING
TO THE MANUFACTURERS INSTRUCTIONS.

Mute

Beeper

XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 11 of 36

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

Relay 1

NC     C     NO

Relay 2

NC     C     NO

Relay 3

NC     C     NO

Fault

NC     C     NO

4

3

4

3

4

3

4

3

NVM ‘memory unlock’ link, 
must be fitted when 
uploading or downloading 
information from/to the PC

Plug the lead’s ‘D’-type connector 
into the appropriate serial socket 
(com1, com2, etc) on the PC

Fig. 8 : Relay output detail

Fig. 9 : Connecting a PC to the panel’s RS232 connector

+

+

+

I

+

+

I

+

Location of small

sized batteries

typically 1.2 Ah

Location of medium

sized batteries
typically 2.1 Ah

+

+

+

Take care to arrange 

batteries so terminals 

do not touch

Location of large

sized batteries 

typically 3.0 Ah

Connection of leads 

to Power Supply PCB

Run the battery leads

(supplied) through slits 

in the plastic ribs 

R E D
BLACK

Nylon

tie wraps

Link wire

Remote PC connection 

 

A four-way RS232 molex connector 
is provided on the Main Control PCB 
for the connection of a Windows 
based PC for programming 
purposes. 
The ONLY way to program this fire 
panel is using a PC loaded with the 
panel’s sophisticated programming 
tools (Part No. XFP507). The lead 
supplied with the software tools 
should be connected to the panel 
and the PC as shown in Fig. 9 (right).

Aux. 24V output

 

 

One fused 24V d.c. output, rated at 100mA, is provided and can be used for supplying power to ancillary 
fire alarm equipment.

Installing the standby battery supply 

 

There is a risk of explosion if incorrect battery types or sizes are used. Always replace both 
batteries and always dispose of used batteries in accordance with the battery manufacturers 
instructions and local regulations. Batteries are heavy and can produce dangerously high currents 
if shorted. Take care when handling and routing battery leads to avoid damage. 

Two new, good quality and fully charged 12V valve regulated lead acid batteries are required as the 
emergency stand-by power supply for the panel. The batteries should be connected in series and located 
in the panel’s enclosure as shown in Fig. 10 below. The battery leads, link wire and nylon cable ties are 
provided in the panel’s accessory pack. Run the battery leads through the slits in the panel’s lower 
plastic ribs and secure the batteries into position using the nylon cable ties as shown. 

 
The panel’s sophisticated battery monitoring unit protects the batteries against deep discharge by 
activating a cut off circuit when the stand-by supply voltage reaches 21V approx. If batteries are not 
fitted, are discharged or in poor condition, a PSU fault will show at the panel. 

 
The capacity of the batteries used will depend upon the required stand-by time. To calculate the 
batteries required for any given stand-by period, refer to the battery calculation guide on page 35. 

 
Fig. 10 : Battery location and connection details

Relay 1 : Switches when any zone goes into fire, switches back when the panel is silenced; 
Relay 2 : Switches when any zone goes into fire, switches back when the panel is reset; 
Relay 3 : Has no default operation.

The wiring for each output should be connected to the 
relevant connector block on the Main Control PCB 
(remember to isolate the panel’s Mains and battery 
backup supplies before making any connections). 
Fig. 8 (right) explains how the outputs work. 

Содержание XFP501E/H

Страница 1: ...XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL Single Loop 16 Zone Version Part Nos XFP501E X XFP501E H engineering manual Approved Document No DFU1200510 Rev 3...

Страница 2: ...Fitting the panel s NVM memory unlock link 18 A detailed description of the functions available at access level 19 33 Maintenance 34 Standby battery calculation guide 35 Technical specification 36 XF...

Страница 3: ...tem is commissioned and serviced in accordance with the laid down specification and national standards If in doubt please consult your supplier We recommend you read BS 5839 Part 1 Fire Detection and...

Страница 4: ...er or not it operates in day night mode which works as follows When there is an alarm in a zone programmed to operate in investigate mode the full alarm condition will occur after a delay It is possib...

Страница 5: ...irst fix installation to protect the electronics from damage Removing the lid and base PCBs Fig 1 Location of the panel s base PCBs and removal details 1 Take the panel out of its box and undo the two...

Страница 6: ...panel to ensure straightforward connection of the field wiring to the panel s terminals Drill centre points are provided in the panel base to aid drilling tools Cut out suitable holes in the panel us...

Страница 7: ...V V V HRC F F 1 1A 2 0 50 250 0 0 V V 0V V V V V HRC V 0V V 0 HR R V V 0V 1A 250 R 1A R THIS WAY UP CONN1 N L Mains Input CONN1 L Live BROWN N Neutral BLUE Earth GREEN YELLOW The incoming Mains earth...

Страница 8: ...o devices will lost since communication is from both ends of the loop but a loop integrity fault will be shown Note that a critical design issue with any analogue fire system is the combined effect of...

Страница 9: ...etaining screws are properly tightened before oper ation as they play an important part in the electrical safety and EMC immunity of the panel Fig 5 Typical analogue addressable loop connection GENERA...

Страница 10: ...inal block marked Auxiliary on the Main Control PCB as shown in Fig 7 right Remember to isolate the panel s Mains and battery backup supplies before making any connections If applicable i e in electri...

Страница 11: ...vided and can be used for supplying power to ancillary fire alarm equipment Installing the standby battery supply There is a risk of explosion if incorrect battery types or sizes are used Always repla...

Страница 12: ...interconnection of up to eight XFP main panels any mix of single loop 16 zone XFPs and 1 and 2 loop 32 zone XFPs Up to 1 km of cable may be fitted to an XFP main panel network Each networked XFP main...

Страница 13: ...allation where pertinent see cable types limitations page 3 A typical XFP main panel non redundant network A typical XFP repeater non redundant network SPUR WIRING NOT ALLOWED SPUR WIRING NOT ALLOWED...

Страница 14: ...rm is silenced Subsequent fire conditions will restart the General Fire indicator flashing until it is silenced again Fire Zones 1 16 One or more of these indicators will flash red in an alarm conditi...

Страница 15: ...nt settings etc serve as code input buttons to access levels 2 or 3 Accept 4 2 Dependent on the status of the panel these two buttons Escape 34 scroll horizontally through the panel s user menus escap...

Страница 16: ...the protocol of the panel etc Investigate any faults reported on the panel s display and take the necessary steps to correct them When all faults have been corrected carry out a loop learn as detaile...

Страница 17: ...LE DISABLE OUTPUTS ENABLE DISABLE RELAYS ENABLE DISABLE DEVICES ENABLE DISABLE FAULT RELAY ENABLE DISABLE OUTPUT DELAYS ENTER ACCESS LEVEL 2 DISPLAY FIRE EVENTS DISPLAY FAULT EVENTS DISPLAY DISABLEMEN...

Страница 18: ...de range of commissioning functions including auto loop learn device calibration and group zone assignment Gain access to a wide range of engineering test and fault finding functions Ascertain softwar...

Страница 19: ...level 3 menu press the Escape3button Display Zones In Test This function is only available if one or more zones are being tested If available press the Accept4button and a window similar to the one b...

Страница 20: ...T COMMS FUNCTION This function allows you to set the panel s RS485 comms to operate in Network or Repeater mode When selected press the Accept4button and a message similar to the one below will appear...

Страница 21: ...been programmed or if you want to program an existing system as if it were a new system press the Accept4button The following message will appear Press the Accept4button again and the panel will erase...

Страница 22: ...or group and press the Accept4button The device search will now continue until the next new device is found Note that I O units etc can only be assigned to output sets via the panel s programming too...

Страница 23: ...software tools must be used to assign them to output sets CALIBRATE DEVICES Daily calibration of the system s smoke and heat detectors to take into account environmental changes drift compensation fa...

Страница 24: ...licate address to check SET DAY NIGHT TIMES This function allows the user to alter the time the panel enters day building occupied and night building unoccupied mode WE RECOMMEND YOU DO NOT USE THIS F...

Страница 25: ...pre alarms etc and is normally used to tem porarily disable a zone of detectors call points in areas such as loading bays that are prone to nuisance triggering from vehicle fumes When selected press...

Страница 26: ...abled from reporting faults fires pre alarms etc and is normally used to temporarily disable detectors call points that are nuisance tripping When selected press the Accept4button and a window similar...

Страница 27: ...O unit is functioning correctly Addressable devices typically have three output chan nels 1 2 and 3 the functions of which depend upon its type please refer to the device manufac turers technical data...

Страница 28: ...groups 1 to 16 by altering its their state between Silenced Intermittent and Continuous When the TEST SOUNDER GROUP prompt appears press the Accept4button and the sounder group selection window will a...

Страница 29: ...ct the test to be carried out from either end of the loop or from both ends at the same time An example illustration of how this test may be carried out is shown below When the BLINK DETECTOR LEDs pro...

Страница 30: ...cepted the device s output bits sequence by pressing the Accept4 button the test will begin and the panel will display the device s current analogue values for example As the device is intensively pol...

Страница 31: ...o assert output channels 1 and 3 of the device being viewed press the More Information button You will be presented with a window similar to the one below In the case of detectors and manual call poin...

Страница 32: ...ng correctly Mis matched numbers i e 49191 40286 indicate that the panel s memory may be corrupt After five seconds the panel will return to the Engineering Functions submenu SHOW PSU STATS This funct...

Страница 33: ...upon the size of the loop and the number of items connected Press the Escape3 button to return to the Engineering Functions submenu SHOW DISCOVERY EEPROM This function allows the panel to interrogate...

Страница 34: ...tenance and installation regulations The Fire Alarm panel s standby batteries should be checked for integrity of the connections deposits indicating venting and a periodic load test with the Mains sup...

Страница 35: ...guideline the average quiescent current addressable devices is typically 0 00025A 250 A To obtain accurate figures consult the device manufacturers own specifications A The total alarm current of the...

Страница 36: ...tage 27V d c non latching Programmed from cause effect Input 2 Connect to 0V to trigger Max input voltage 27V d c non latching Programmed from cause effect FUSES IEC EN60127 Pt2 Primary fuse T 1A H 23...

Отзывы: