XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 24 of 36
If there are multiple addresses with calibration issues, press the
5
button to scroll to the next affected address.
Press the Accept
4
button and output channels 1 and 3 of the detector being viewed will be asserted.
Once activated, you will be given the option to switch off output channels 1 and 3 by pressing the
Accept
4
button again. Press the Escape
3
button as appropriate to return to the previous menus or to
select another device with calibration issues.
SHOW DUPLICATE ADDRESSES
This function helps you to locate devices with duplicate addresses by asserting their output channels 1&3.
In the case of detectors and manual call points, activating these channels will turn their LEDs on.
Caution:
Note that channels 1 & 3 on an I/O unit may be programmed to trigger say, a water
extinguishant system, so this function must be used with care. Activating channels 1 and 3 on a
sounder/beacon will have no effect.
When the SHOW DUPLICATE DEVICES prompt is accepted, details of the first double address will
appear. For example:
If there are multiple duplicate addresses, press the
5
button to scroll to the next affected address.
Press the More Information button at any time and a window similar to the one below will appear:
If you are confident to proceed, press the Accept
4
button and output channels 1 and 3 of all devices
with the duplicate address being viewed will be asserted.
Once activated, you will be given the option to switch off output channels 1 and 3 by pressing the
Accept
4
button again. Press the Escape
3
button as appropriate to return to the previous menus or to
select another duplicate address to check.
SET DAY/NIGHT TIMES
This function allows the user to alter the time the panel enters day (building occupied) and night
(building unoccupied) mode. WE RECOMMEND YOU DO NOT USE THIS FUNCTION UNLESS YOU ARE
INTIMATELY FAMILIAR WITH THE OPERATION OF THE FIRE ALARM SYSTEM.
Changes that may take place when the panel is in day/night mode include detector sensitivities (how
quick a detector reacts in the event of a fire), cause and effects (what happens in the event of a fire)
and sounder volumes (if available). These changes can only be made by an authorised engineer using
the panel’s sophisticated programming tools at access level 3. If in doubt, refer to page 20 where any
day/night changes will be recorded, provided it has been completed by the system engineer.
When the SET/DAY NIGHT TIMES prompt appears, press the Accept
4
button and the following win-
dow (or similar) will appear:
Use the
5
and
6
buttons to set the time in hours that you want the panel to enter day mode (the
panel has a 24 hour clock so hours 0 to 23 are available).
When the correct hour is displayed, press the Accept
4
button to move to the minutes field.
Use the
5
and
6
buttons to set the time in minutes you want the panel to enter day mode.
When the desired time is displayed, press the Accept
4
button to access the night mode entry field.
A window similar to the one below will appear:
Use the scroll
56
and Accept
4
buttons to set the time in hours and minutes that you want the
panel to enter night mode. When the desired time is displayed, press the Accept
4
button again and
you will be returned to the commissioning functions submenu.
XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Loop: 1 Devi
c
e: 23 :Dupli
c
ate A
dd
ress
Turn ON output
c
hannels 1&3
Loop: 1 Devi
c
e: 23 :Dupli
c
ate A
dd
ress
Day (O
cc
upie
d
) mo
d
e
b
e
g
ins:- 0
6
:00
Day (O
cc
upie
d
) mo
d
e
b
e
g
ins:- 0
6
:00
Ni
g
ht (Un-O
cc
upie
d
) mo
d
e
b
e
g
ins:- 18:00