Fig. 11: Installing the network communication card

 

 
Important: Before installing the network communication card, isolate the Mains supply and 
disconnect the panel’s battery back-up supply. With reference to the diagram below: 

 

 

•  Secure the card inside the panel using the two 

   retaining screws provided. 

 
•  Connect the two-way polarised power supply loom 

   (supplied with the card) between PL1 on the card 
   and PL2 on the Power Supply PCB. 

 
•  Connect the 8-way telecoms-style connector cable 

   (also supplied with the card) between PL2 on the 
   card and the socket on the reverse of the Main 
   Control PCB (socket SK2 which is located alongside 
   the PCB’s microprocessor).

 

 

 

Note:

 The DIP switch (SW1) on the network 

communication card has no function when used 
with the XFP. However, all networked XFP main 
panels require a unique ID number (1-8) so they 
can be recognised by other panels on the 
network. This is assigned using the NETWORK 
FUNCTIONS menu option at access level 3. 
XFP repeaters DO NOT require an ID number.

XFP ENGINEERING MANUAL • Approved Document No. DFU1200510 Rev 3 • Page 12 of 36

XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

To SK2 on
the reverse
of the Main
Control PCB

PL2

PL1

PL2

PL1

POWER
SUPPLY
PCB

NETWORK
DRIVER
CARD

To SK1 on
the reverse
of the Main
Control PCB

A B C A B

Network/repeater wiring (optional) 

 

The XFP’s network protocol allows the connection of up to eight XFP main panels (any variant) over a    
2-wire RS485 non-redundant network. Alternatively, the network can be used to connect up to eight XFP 
repeaters to one non-networked XFP main panel. 
It is 

NOT

 possible to mix XFP main panels and XFP repeaters on the same network. 

 

Key features of the non-redundant network protocol when used for interconnecting XFP main panels: 

  

•   Allows the interconnection of up to eight XFP main panels (any mix of single loop 16 zone XFPs and 

    1 and 2 loop 32 zone XFPs) 

 
•   Up to 1 km of cable may be fitted to an XFP main panel network.  

 
•   Each networked XFP main panel can be programmed to:  

    Accept Fires from other main panels.  
    Accept Faults from other main panels. 
    Accept Control actions such as Silence Alarm Sounders and Control Panel Reset from other main panels. 
    Accept Disablement commands for zones, sounders and output sets from other main panels.  
    (Each of these four functions may be individually selected via the panel’s PC Programming Software Tools.) 

 
•   All panels monitor all other panels for network wiring faults. 

 
•   Fires on remote panels are displayed on local panels including the point description of the alarm’s origin. 

 
•   Faults on remote panels are displayed on local panels. 

 
•   Cause and effect can be programmed into local panels dependent on which remote panel is in alarm. 

 
•   The network supports the programming of site information into remote panels from a PC connected 

    at a local panel.  

 
•   Time and date is common to all panels throughout the network.  
 

Key features of the non-redundant network protocol when used for connecting XFP repeaters 

 

•   Allows the connection of up to eight XFP repeaters (any mix of single loop 16 zone repeaters and 

    1 or 2 loop 32 zone repeaters) 

to any non-networked main panel.

 

 
•   Up to 500m of cable may be fitted to an XFP repeater network. 

 
•   Each XFP repeater offers all the functions and controls of an XFP main panel  
 

Any XFP main panel connected to the non-redundant network requires the installation of a Network 
Communication Card (Part No. XFP761), as shown in Fig. 11 below. (Repeaters come with a Network 
Communication Card already fitted). Typical network wiring details are shown in Fig. 12.

To SK2 on 
the main 
control 
PCB

To SK1 on 
the main 
control PCB

See Fig. 12 for typical  

network wiring details

Note: The XFP network and XFP repeaters have 
not been assessed to EN54-2.

Содержание XFP501E/H

Страница 1: ...XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL Single Loop 16 Zone Version Part Nos XFP501E X XFP501E H engineering manual Approved Document No DFU1200510 Rev 3...

Страница 2: ...Fitting the panel s NVM memory unlock link 18 A detailed description of the functions available at access level 19 33 Maintenance 34 Standby battery calculation guide 35 Technical specification 36 XF...

Страница 3: ...tem is commissioned and serviced in accordance with the laid down specification and national standards If in doubt please consult your supplier We recommend you read BS 5839 Part 1 Fire Detection and...

Страница 4: ...er or not it operates in day night mode which works as follows When there is an alarm in a zone programmed to operate in investigate mode the full alarm condition will occur after a delay It is possib...

Страница 5: ...irst fix installation to protect the electronics from damage Removing the lid and base PCBs Fig 1 Location of the panel s base PCBs and removal details 1 Take the panel out of its box and undo the two...

Страница 6: ...panel to ensure straightforward connection of the field wiring to the panel s terminals Drill centre points are provided in the panel base to aid drilling tools Cut out suitable holes in the panel us...

Страница 7: ...V V V HRC F F 1 1A 2 0 50 250 0 0 V V 0V V V V V HRC V 0V V 0 HR R V V 0V 1A 250 R 1A R THIS WAY UP CONN1 N L Mains Input CONN1 L Live BROWN N Neutral BLUE Earth GREEN YELLOW The incoming Mains earth...

Страница 8: ...o devices will lost since communication is from both ends of the loop but a loop integrity fault will be shown Note that a critical design issue with any analogue fire system is the combined effect of...

Страница 9: ...etaining screws are properly tightened before oper ation as they play an important part in the electrical safety and EMC immunity of the panel Fig 5 Typical analogue addressable loop connection GENERA...

Страница 10: ...inal block marked Auxiliary on the Main Control PCB as shown in Fig 7 right Remember to isolate the panel s Mains and battery backup supplies before making any connections If applicable i e in electri...

Страница 11: ...vided and can be used for supplying power to ancillary fire alarm equipment Installing the standby battery supply There is a risk of explosion if incorrect battery types or sizes are used Always repla...

Страница 12: ...interconnection of up to eight XFP main panels any mix of single loop 16 zone XFPs and 1 and 2 loop 32 zone XFPs Up to 1 km of cable may be fitted to an XFP main panel network Each networked XFP main...

Страница 13: ...allation where pertinent see cable types limitations page 3 A typical XFP main panel non redundant network A typical XFP repeater non redundant network SPUR WIRING NOT ALLOWED SPUR WIRING NOT ALLOWED...

Страница 14: ...rm is silenced Subsequent fire conditions will restart the General Fire indicator flashing until it is silenced again Fire Zones 1 16 One or more of these indicators will flash red in an alarm conditi...

Страница 15: ...nt settings etc serve as code input buttons to access levels 2 or 3 Accept 4 2 Dependent on the status of the panel these two buttons Escape 34 scroll horizontally through the panel s user menus escap...

Страница 16: ...the protocol of the panel etc Investigate any faults reported on the panel s display and take the necessary steps to correct them When all faults have been corrected carry out a loop learn as detaile...

Страница 17: ...LE DISABLE OUTPUTS ENABLE DISABLE RELAYS ENABLE DISABLE DEVICES ENABLE DISABLE FAULT RELAY ENABLE DISABLE OUTPUT DELAYS ENTER ACCESS LEVEL 2 DISPLAY FIRE EVENTS DISPLAY FAULT EVENTS DISPLAY DISABLEMEN...

Страница 18: ...de range of commissioning functions including auto loop learn device calibration and group zone assignment Gain access to a wide range of engineering test and fault finding functions Ascertain softwar...

Страница 19: ...level 3 menu press the Escape3button Display Zones In Test This function is only available if one or more zones are being tested If available press the Accept4button and a window similar to the one b...

Страница 20: ...T COMMS FUNCTION This function allows you to set the panel s RS485 comms to operate in Network or Repeater mode When selected press the Accept4button and a message similar to the one below will appear...

Страница 21: ...been programmed or if you want to program an existing system as if it were a new system press the Accept4button The following message will appear Press the Accept4button again and the panel will erase...

Страница 22: ...or group and press the Accept4button The device search will now continue until the next new device is found Note that I O units etc can only be assigned to output sets via the panel s programming too...

Страница 23: ...software tools must be used to assign them to output sets CALIBRATE DEVICES Daily calibration of the system s smoke and heat detectors to take into account environmental changes drift compensation fa...

Страница 24: ...licate address to check SET DAY NIGHT TIMES This function allows the user to alter the time the panel enters day building occupied and night building unoccupied mode WE RECOMMEND YOU DO NOT USE THIS F...

Страница 25: ...pre alarms etc and is normally used to tem porarily disable a zone of detectors call points in areas such as loading bays that are prone to nuisance triggering from vehicle fumes When selected press...

Страница 26: ...abled from reporting faults fires pre alarms etc and is normally used to temporarily disable detectors call points that are nuisance tripping When selected press the Accept4button and a window similar...

Страница 27: ...O unit is functioning correctly Addressable devices typically have three output chan nels 1 2 and 3 the functions of which depend upon its type please refer to the device manufac turers technical data...

Страница 28: ...groups 1 to 16 by altering its their state between Silenced Intermittent and Continuous When the TEST SOUNDER GROUP prompt appears press the Accept4button and the sounder group selection window will a...

Страница 29: ...ct the test to be carried out from either end of the loop or from both ends at the same time An example illustration of how this test may be carried out is shown below When the BLINK DETECTOR LEDs pro...

Страница 30: ...cepted the device s output bits sequence by pressing the Accept4 button the test will begin and the panel will display the device s current analogue values for example As the device is intensively pol...

Страница 31: ...o assert output channels 1 and 3 of the device being viewed press the More Information button You will be presented with a window similar to the one below In the case of detectors and manual call poin...

Страница 32: ...ng correctly Mis matched numbers i e 49191 40286 indicate that the panel s memory may be corrupt After five seconds the panel will return to the Engineering Functions submenu SHOW PSU STATS This funct...

Страница 33: ...upon the size of the loop and the number of items connected Press the Escape3 button to return to the Engineering Functions submenu SHOW DISCOVERY EEPROM This function allows the panel to interrogate...

Страница 34: ...tenance and installation regulations The Fire Alarm panel s standby batteries should be checked for integrity of the connections deposits indicating venting and a periodic load test with the Mains sup...

Страница 35: ...guideline the average quiescent current addressable devices is typically 0 00025A 250 A To obtain accurate figures consult the device manufacturers own specifications A The total alarm current of the...

Страница 36: ...tage 27V d c non latching Programmed from cause effect Input 2 Connect to 0V to trigger Max input voltage 27V d c non latching Programmed from cause effect FUSES IEC EN60127 Pt2 Primary fuse T 1A H 23...

Отзывы: