Basic Functional Test—Multiple Inverters
975-0384-01-02
2–37
This manual for use by qualified personnel only
Figure 2-23
Functional Test for Multiple Inverters - Page 2 of 2
From previous page...
Use Xantrex
XW SCP to
enable system
Set System
Mode to
Operating
Use Xantrex XW
SCP to enable
both inverters
Use System Settings
to enable invert mode
on both inverters
Confirm invert
mode has
been enabled
Check
display for
Faults
Faults?
Yes
Correct fault
condition. Restart
functional test.
No
Check AC voltage at
terminals of Master
Close both AC
load breakers
Confirm
operation of
AC load
Disconnect
AC load
breakers
Proceed to
Charger
Functional Test
Master
Master
Slave
Slave
Confirm that Master
shows output but Slave
is not inverting
Check for faults on both
information panels and
Xantrex XW SCP