
Inverter/Charger Installation
2–14
975-0384-01-02
This manual for use by qualified personnel only
Inverter Grounding
The Xantrex XW Inverter/Charger and Xantrex XW Solar Charge Controller are
provided with ground terminals that must be reliably connected to ground
(protective earth) by appropriately sized equipment grounding conductors.
System grounding for the AC and DC systems must be done according to code.
Refer to the grounding information in this manual and all applicable installation
codes.
Feed-in Protection Requirements
Table 2-5
Torque Values for the Chassis Ground Lug
Wire Size
Torque Value
AWG
mm
2
In-lb
N-m
6–4
16–25
45
5.1
3–2
25–35
50
5.6
Table 2-6
Torque Values for the Inverter Battery Terminals
Torque Value
Ft-lbs
N-m
15
20.4
Important:
The grounding requirements vary by country and by application. All
installations must comply with national and local codes. Consult local and
national codes for specific grounding and bonding requirements for the desired
installation.
Important:
Installers must make allowance for the amount of power that can be
fed into a distribution panel and the means and location for feed-in, in
accordance with local electrical code.
Содержание XW4024 230 50
Страница 2: ...YOUR SCHNEIDER ELECTRIC DISTRIBUTOR SOLIGENT 800 967 6917 www soligent net...
Страница 3: ...Xantrex XW Hybrid Inverter Charger Installation Guide www schneider electric com...
Страница 8: ...vi...
Страница 18: ...1 8...
Страница 56: ...2 38...
Страница 66: ...IX 2...
Страница 67: ......