Step 4: Wiring the Inverter
975-0384-01-02
2–17
This manual for use by qualified personnel only
7.
Connect the other end of the cable to the NEGATIVE (–) terminal on the
battery.
8.
Use a wrench to tighten the bolt to the required torque.
9.
Attach the DC terminal covers.
Important:
The next step is the last cable connection. A spark is normal when
this connection is made.
Figure 2-10
Battery Cable Connection
CAUTION: Damage to Equipment
Do not put anything between the battery cable lug and the terminal surface.
Overheating of the terminal may occur. Do not apply any type of antioxidant
paste until after the battery cable wiring is tightened. The same applies for all DC
connections. Do not over-tighten; observe all recommended torque values.
CAUTION: Reverse Polarity Damage
Before making the final DC connection or closing the DC breaker or disconnect,
check cable polarity at both the battery and the inverter/charger. Positive (+)
must be connected to positive (+). Negative (–) must be connected to
negative (–).
Reverse polarity damage is not covered by warranty.
Terminal surface
Copper compression lug
Make sure nothing is between the terminal
surface and the battery cable lug
Battery cable lug
Flat washer
3/8-15 x 5/8” bolt (supplied)
Shrink-wrap to
color-code the cable
Split-ring lock washer
Содержание XW4024 230 50
Страница 2: ...YOUR SCHNEIDER ELECTRIC DISTRIBUTOR SOLIGENT 800 967 6917 www soligent net...
Страница 3: ...Xantrex XW Hybrid Inverter Charger Installation Guide www schneider electric com...
Страница 8: ...vi...
Страница 18: ...1 8...
Страница 56: ...2 38...
Страница 66: ...IX 2...
Страница 67: ......