Step 4: Wiring the Inverter
975-0239-01-01
2–25
This manual for use by qualified personnel only
AUX-RPO: User Remote Power Off (RPO)
Connecting JU-2 (AUX-RPO) and JU-3 (AUX-COM) terminals together through an
external switch (normal open contact) will provide the system shut off function if the
switch is closed.
The external switch if pressed overrides the control provided from the front panel.
To enable the AUX port remote power off function, the RPO setting must be enabled from
the System Control Panel. For more information, see the XW Inverter/Charger Operation
Guide.
If the external switch is cleared (not pressed), the system can be enabled back from the
front panel.
Select an external switch with normal open contact; consult your local system designer or
qualified technician for specific installation instructions.
User Line Wiring
Use twisted pairs of #24 AWG to #12 AWG for connections. Carefully route the wires
away from high power load cables to minimize noise effects on signal integrity.
AUX Port Terminal Assignments
Table 2-11
User Connector Terminals and Functions
Pin
Reference
Name
Function
JU-1
AUX+12V
+12 V User Voltage
Supply
+12 Vdc Voltage source: 0.25 Adc maximum
JU-2
AUX-RPO
Remote Power Off
Remote Power Off Logic Level: Active Low.
Connecting this signal shuts down system
operation.
JU-3
AUX-COM
Common Ground
Reference
Return Common Ground Reference for 12V,
Remote Power Off signals.
JU-4
Not Operational
Not Operational
Not Operational
JU-5
Not Operational
Not Operational
Not Operational
Содержание XW4024-120/240-60, XW4548-120/240-60,...
Страница 2: ......
Страница 3: ...XW Power System Installation Guide...
Страница 16: ...xvi...
Страница 24: ...1 8...
Страница 70: ...2 46...
Страница 71: ...Basic Functional Test Multiple Inverters 975 0239 01 01 2 47 This manual for use by qualified personnel only...
Страница 72: ...Inverter Charger Installation 2 48 975 0239 01 01 This manual for use by qualified personnel only...
Страница 73: ...Basic Functional Test Multiple Inverters 975 0239 01 01 2 49 This manual for use by qualified personnel only...
Страница 74: ...Inverter Charger Installation 2 50 975 0239 01 01 This manual for use by qualified personnel only...
Страница 118: ...5 20...
Страница 128: ...B 2...
Страница 142: ...C 8...
Страница 145: ......