Inverter/Charger Installation
2–18
975-0239-01-01
This manual for use by qualified personnel only
Grounding the AC System
See Table 2-4 on page 10 for torque values for the AC terminal and AC Ground bar.
See Figure 2-8 on page 2–11 for torque requirements for the ground bar in the XW Power
Distribution Panel.
Important:
Place the neutral-to-ground bond in a permanently installed AC distribution panel that
is part of the system. This may be a main panel or a sub-panel.
Figure 2-16
Grounding the AC System using the Distribution Panel
Actual ground requirements may vary.
* Depending on the location of the generator and
local code requirements, the generator disconnect
may be located in the power distribution panel.
In an off-grid installation (i.e., where no utility grid is available),
the generator can be connected to the breakers provided in the
XW Power Distribution Panel. No additional breaker is required.
*This Grounding Conductor may not be required if the DC ground is used instead.
Only one ground bond from the PDP to the main panel needs to be in place.
Содержание XW4024-120/240-60, XW4548-120/240-60,...
Страница 2: ......
Страница 3: ...XW Power System Installation Guide...
Страница 16: ...xvi...
Страница 24: ...1 8...
Страница 70: ...2 46...
Страница 71: ...Basic Functional Test Multiple Inverters 975 0239 01 01 2 47 This manual for use by qualified personnel only...
Страница 72: ...Inverter Charger Installation 2 48 975 0239 01 01 This manual for use by qualified personnel only...
Страница 73: ...Basic Functional Test Multiple Inverters 975 0239 01 01 2 49 This manual for use by qualified personnel only...
Страница 74: ...Inverter Charger Installation 2 50 975 0239 01 01 This manual for use by qualified personnel only...
Страница 118: ...5 20...
Страница 128: ...B 2...
Страница 142: ...C 8...
Страница 145: ......