This section describes the generator configurations and provides diagrams for connecting
the wiring harness to the generator’s start wiring.
Connecting the Thermostats (optional)
Wires 1, 2, 3, and 4 on the wiring harness can be connected to two thermostats. Wires 1
(yellow) and 2 (gray) are intended for thermostat 1 and wires 3 (orange) and 4 (gray) are
intended for thermostat 2.
These wires connect to 12-volt/24-volt output signals from the thermostats. The XW
Automatic Generator Start will start the generator in response to these signals.
Thermostats can not be programmed using the XW Automatic Generator Start.
For specific information about thermostat wiring and where XW Automatic Generator
Start connections should be made, please consult your thermostat documentation or
contact the thermostat manufacturer.
Connecting an External Shutdown (optional)
The external shutdown input is a 12-volt/24-volt input used to assure that the XW
Automatic Generator Start keeps the generator off under conditions that may be
potentially hazardous. Wire 5 (white/black) and 6 (gray) on the wiring harness are
intended for an external switch or sensor (such as a moisture detector, carbon monoxide
detector or coach running signal) that produces an active high 12-volt or 24-volt output.
Important:
For an explanation of the terminology used in the following section, refer to
Appendix B of the XW Automatic Generator Start Owner’s Guide. For more information about
XW Automatic Generator Start internal relay activity and timing, see the Automatic Generator
Start Owner’s Guide.
Table 5-4
Wiring for Connecting Thermostats
Wire Number
Function
Wiring Harness
Wire Color
1
Thermostat 1 input (12/24 V)
Yellow
2
Thermostat 1 return (ground)
Gray
3
Thermostat 2 input (12/24 V)
Orange
4
Thermostat 2 return (ground)
Gray
Table 5-5
Wiring for Connecting an External Shutdown
Wire number Function
Wiring Harness
Wire Color
5
External shutdown input (12/24 V)
White/Black
6
External shutdown return (ground)
Gray
Содержание XW4024-120/240-60, XW4548-120/240-60,...
Страница 2: ......
Страница 3: ...XW Power System Installation Guide...
Страница 16: ...xvi...
Страница 24: ...1 8...
Страница 70: ...2 46...
Страница 71: ...Basic Functional Test Multiple Inverters 975 0239 01 01 2 47 This manual for use by qualified personnel only...
Страница 72: ...Inverter Charger Installation 2 48 975 0239 01 01 This manual for use by qualified personnel only...
Страница 73: ...Basic Functional Test Multiple Inverters 975 0239 01 01 2 49 This manual for use by qualified personnel only...
Страница 74: ...Inverter Charger Installation 2 50 975 0239 01 01 This manual for use by qualified personnel only...
Страница 118: ...5 20...
Страница 128: ...B 2...
Страница 142: ...C 8...
Страница 145: ......